Effect of Operating Conditions on the Performance of Two-Bed Closed-Cycle Solid-Sorption Heat Pump Systems
暂无分享,去创建一个
The effect of two operating parameters, the regeneration temperature and the ambient temperature, on the performance of two-bed, closed-cycle solid-sorption heat pumps is investigated. The results show that increasing the regeneration temperature can improve both the COP and cooling capacity, and the effect on cooling capacity is more significant than the COP. Increasing the regeneration temperature from 184°C to 260°C, the cooling capacity increases by 50 percent and the COP improves 20 percent. When the ambient temperature drops, the system performance increases significantly. When the ambient temperature decreases by 10°C from the design point of 35°C, the COP and cooling capacity increases by 50 percent and 40 percent, respectively. Also, the bed cycling speed should be increased to achieve the optimum system performance when the regeneration temperature is higher or the ambient temperature becomes lower.
[1] F. Meunier. Theoretical performances of solid adsorbent cascading cycles using the zeolite-water and active carbon-methanol pairs: four case studies , 1986 .
[2] William J. Wepfer,et al. Square wave analysis of the solid-vapor adsorption heat pump , 1989 .
[3] William J. Wepfer,et al. Ramp Wave Analysis of the Solid/Vapor Heat Pump , 1990 .
[4] William M. Worek,et al. Simulation of a regenerative, closed-cycle adsorption cooling/heating system , 1991 .