Comparison of CIGRE Method and IEEE-Flash Software for Back-flashover Rate Calculations☆

Abstract This paper presents the comparison of back-flashover rate (BFR) by applying the CIGRE method and the IEEE-Flash software. The BFR on 230 kV single and double circuits transmission lines have been compared. Firstly, the BFR from the two iterative methods, CIGRE and the simplified methods, have been compared then the BFR using CIGRE method has been chosen in order to compare the results with the IEEE-Flash software. The IEEE-Flash software gives the BFR significantly higher than the CIGRE method for 230 kV double circuits but not for the single circuit.

[1]  T. Thanasaksiri Lightning flashover rates of overhead distribution lines applying volt time curve from testing and IEEE Std.1410-2004 , 2011, The 8th Electrical Engineering/ Electronics, Computer, Telecommunications and Information Technology (ECTI) Association of Thailand - Conference 2011.