Reliability determination of aluminium electrolytic capacitors by the mean of various methods. Application to the protection system of the LHC

The lifetime of power electronic components is often calculated from reliability reports, but this method can be discussed. We compare in this article the results of various reliability reports to an accelerated ageing test of component and introduced the load-strength concept. Large aluminium electrolytic capacitors are taken here in example in the context of the protection system of LHC (Large Hadron Collider) in CERN where the level of reliability is essential. We notice important differences of MTBF (Mean Time Between Failure) according to the reliability report used. Accelerating ageing tests carried out prove that a Weibull law is more adapted to determinate failure rates of components. The load-strength concept associated with accelerated ageing tests can be a solution to determine the lifetime of power electronic components.

[1]  Jeffrey Alun Jones,et al.  A comparison of electronic-reliability prediction models , 1999 .

[2]  Michael L. Gasperi,et al.  Life prediction model for aluminum electrolytic capacitors , 1996, IAS '96. Conference Record of the 1996 IEEE Industry Applications Conference Thirty-First IAS Annual Meeting.

[3]  F. Jensen Electronic component reliability , 1999, IEEE Aerospace and Electronic Systems Magazine.

[4]  P. A. Stokes Engineering reliability and long life design , 1965 .