A self-calibrating high-precision current transformer
暂无分享,去创建一个
A self-calibrating current transformer with nominal ratio 10 A to 100 mA, intended for low frequencies applications, was developed. It has 100 independent primary windings to be connected in series or parallel, so that it can be configured as 100:1 or 1:1 transformer (all windings in series). This last ratio permits autocalibration. Error sources are analyzed, and it is shown that differences between parallel and series configurations have uncertainties lower than 1 part in 106.
[1] T. Michael Souders,et al. Wide-Band Two-Stage Current Transformers of High Accuracy , 1972 .
[2] Daniel Slomovitz,et al. Electronic error reduction system for clamp-on probes and measuring current transformers , 2000, IEEE Trans. Instrum. Meas..
[3] N. L. Kusters,et al. Correction [to "The compensated current comparator; A new reference standard for current-transformer calibrations in industry"] , 1964 .