Fault Prediction for Power Transformer Using Optical Spectrum of Transformer Oil and Data Mining Analysis

Periodic preventive maintenance of power transformer should be conducted for its health monitoring and early fault detection. Transformer oil is a vital element where its contents and properties need to be monitored during the service life of a power transformer. This paper presents an optical spectroscopy measurement from 200 nm to 3300 nm to characterize the transformer oil, which were sampled from the main tanks and ‘on-load tap changer’ of power transformers. The correlation of the optical characteristics in the range of 2120 nm to 2220 nm to the Dissolved Gas Analysis results and Duval Triangle interpretation demonstrates that the low energy electrical discharges, high energy electrical discharges as well as the thermal faults rated at temperatures above 700°C in power transformers can be accurately predicted. For faster and accurate analysis of fault prediction, a data mining analytics tool was constructed using Rapid Miner server to analyze and verify the predictions for a total of 108 oil samples. For the optimization, continuous iterations were performed to determine the best absorbance-wavelength combination that can improve the accuracy of the prediction. The performance of the optical spectroscopy technique integrated with data analytic tool was analyzed and it was found that the technique contributes to a high accuracy of 98.1% in fault prediction. It is a cost-effective and quicker complementing approach to carry out pre-screening of the transformer oil in order to know the condition of the power transformers based on the transformer oil’s optical characteristics.

[1]  V. Ebert,et al.  Sensitive detection of methane with a 1.65 μm diode laser by photoacoustic and absorption spectroscopy , 1998 .

[2]  Stefan Tenbohlen,et al.  Detection and quantitative diagnosis of axial displacement of transformer winding by frequency response analysis , 2019, IET Generation, Transmission & Distribution.

[3]  D. Skelly,et al.  Photo-acoustic spectroscopy for dissolved gas analysis: Benefits and Experience , 2012, 2012 IEEE International Conference on Condition Monitoring and Diagnosis.

[4]  Hamza Houassine,et al.  Enhanced modelling of the transformer winding high frequency parameters identification from measured frequency response analysis , 2019 .

[5]  Pin Jern Ker,et al.  Detection of 2FAL Furanic Compound in Transformer Oil Using Optical Spectroscopy Method and Verification Using Morse Oscillation Theory , 2020, IEEE Access.

[6]  Sherif S. M. Ghoneim,et al.  Improvement of Rogers four ratios and IEC Code methods for transformer fault diagnosis based on Dissolved Gas Analysis , 2015, 2015 North American Power Symposium (NAPS).

[7]  A. Cavallini,et al.  Analysis on partial discharge propagation and detection in MV power transformers , 2009, 2009 IEEE Conference on Electrical Insulation and Dielectric Phenomena.

[8]  Zhixin Mao,et al.  Detection of dissolved gas in oil–insulated electrical apparatus by photoacoustic spectroscopy , 2015, IEEE Electrical Insulation Magazine.

[9]  V. P. Darabad,et al.  A novel method for differentiating and clustering multiple partial discharge sources using S transform and bag of words feature , 2017, IEEE Transactions on Dielectrics and Electrical Insulation.

[10]  Michel Duval,et al.  A review of faults detectable by gas-in-oil analysis in transformers , 2002 .

[11]  Ahmed Abu-Siada,et al.  3D approach for fault identification within power transformers using frequency response analysis , 2019 .

[12]  A. Abu-Siada,et al.  A new method to detect dissolved gases in transformer oil using NIR-IR spectroscopy , 2017, IEEE Transactions on Dielectrics and Electrical Insulation.

[13]  Detection of Dissolved Carbon Monoxide in Transformer Oil Using 1.567 m Diode Laser-Based Photoacoustic Spectroscopy , 2015 .

[14]  T.R. Blackburn,et al.  Comparative Study and Analysis of DGA Methods for Transformer Mineral Oil , 2007, 2007 IEEE Lausanne Power Tech.

[15]  Sukhbir Singh,et al.  Duval Triangle: A Noble Technique for DGA in Power Transformers , 2010 .

[16]  Xinlei Zhou,et al.  Dissolved Gas-in-Oil Analysis in Transformers Based on Near-Infrared Photoacoustic Spectroscopy , 2015 .

[17]  Osama E. Gouda,et al.  Condition assessment of power transformers based on dissolved gas analysis , 2019 .

[18]  T. Leibfried,et al.  Postmortem Investigation of Power Transformers—Profile of Degree of Polymerization and Correlation With Furan Concentration in the Oil , 2013, IEEE Transactions on Power Delivery.

[19]  Min Chen,et al.  Dynamic Fault Prediction of Power Transformers Based on Hidden Markov Model of Dissolved Gases Analysis , 2019, IEEE Transactions on Power Delivery.

[20]  Y. Izawa,et al.  Analysis of dissolved C2H2 in transformer oils using laser Raman spectroscopy. , 2013, Optics letters.

[21]  A. Ismail,et al.  New near-infrared absorbance peak for inhibitor content detection in transformer insulating oil , 2018 .

[22]  Sebastian Borucki,et al.  Measurements on partial discharge in on-site operating power transformer: a case study , 2018 .

[23]  P. Rapisarda,et al.  Classification and localisation of multiple partial discharge sources within a high voltage transformer winding , 2016, 2016 IEEE Electrical Insulation Conference (EIC).

[24]  M. Z. Jamaludin,et al.  Detection of Power Transformer Fault Conditions using Optical Characteristics of Transformer Oil , 2018, 2018 IEEE 7th International Conference on Photonics (ICP).

[25]  Weigen Chen,et al.  The research on simultaneous detection of dissolved gases in transformer oil using Raman spectroscopy , 2014, 2014 International Conference on Advances in Communication and Computing Technologies (ICACACT 2014).