저압 전원계통 접지방식별 뇌서지보호성능

The grounding system of low voltage power systems is TT grounding system in Korea. In order to follow the international standard, TN grounding system is adopted. However, the performance of grounding systems has not been evaluated. This paper deals with the experimental results of protection ability of grounding system when lightning surge invades to the neutral line of low voltage power system. As a result, the TT grounding system is most frail for the lightning surge and it does not protect the electrical devices. On the other hand, the TN grounding system perfectly protects the electrical equipment and prevents the electric shock for human through the equipotential bonding. In case of TN system with supplement grounding, it is very important to lower the supplement grounding resistance to protect the electrical equipment and electric shock for human.