The impact of the induction motor on short-circuit current
暂无分享,去创建一个
Simplified analytical models for calculation of the induction motor's short-circuit current are presented. Laboratory tests have been performed on two induction motors with low power rating, 26 kW and 122 kW, respectively, in order to measure their short-circuit current. Results calculated according to the available literature have been compared to those acquired by testing. Calculations have also been made for a high-voltage induction motor rated 1250 kW, whose parameters have been known.
[1] Ronald G. Harley,et al. The General Theory of Alternating Current Machines , 1975 .