First-Zone Distance Relaying Algorithm of Parallel Transmission Lines for Cross-Country Grounded Faults

A novel distance protection algorithm for the first-zone distance relay of parallel transmission lines is proposed for cross-country grounded faults. The algorithm calculates the fault impedance using one-end sampling voltages and currents from a single line. The theoretical basis of the proposed algorithm is described in this paper, which is based on the symmetrical component method for parallel lines. And an attempt is made to express the zero-sequence current of the adjacent parallel line at the relay location by the zero-sequence current of the concerned line in combination with the fault characteristics of the system model, by which the impact of the mutual coupling between the lines can be eliminated. And, thus, the distance algorithm for cross-country grounded faults is presented. The simulations show that the proposed algorithm can obtain the accurate fault reactance when cross-country bolted faults occur, which is superior to the existing distance protection algorithm based on one-end data from a single line.

[1]  Wang Zhigang,et al.  Fault location of two-parallel transmission line for non-earth fault using one-terminal data , 1999 .

[2]  B.R. Bhalja,et al.  High-Resistance Faults on Two Terminal Parallel Transmission Line: Analysis, Simulation Studies, and an Adaptive Distance Relaying Scheme , 2007, IEEE Transactions on Power Delivery.

[3]  H. Khorashadi-Zadeh,et al.  Artificial neural network approach to fault classification for double circuit transmission lines , 2004, 2004 IEEE/PES Transmision and Distribution Conference and Exposition: Latin America (IEEE Cat. No. 04EX956).

[4]  G. W. Swift,et al.  Enhanced double circuit line protection , 1997 .

[5]  S.F. Huang,et al.  A Distance Protection Relay for a 1000-kV UHV Transmission Line , 2008, IEEE Transactions on Power Delivery.

[6]  A. Wiszniewski Accurate fault impedance locating algorithm , 1983 .

[7]  L. van der Sluis,et al.  Adaptive distance protection of a double-circuit line using artificial neural nets , 1994 .

[8]  A. G. Phadke,et al.  A New Computer Based Integrated Distance Relay For Parallel Transmission Lines , 1985, IEEE Transactions on Power Apparatus and Systems.

[9]  S. Elangovan,et al.  Digital distance relaying algorithm for first-zone protection for parallel transmission lines , 1998 .

[10]  Z. Y. Xu,et al.  First-Zone Distance Relaying Algorithm of Parallel Transmission Lines for Cross-Country Nonearthed Faults , 2011, IEEE Transactions on Power Delivery.

[11]  Om P. Malik,et al.  A digital protection technique for parallel transmission lines using a single relay at each end , 1992 .

[12]  V. Leitloff,et al.  An Adaptive Scheme for Parallel Line Distance Protection , 2001, IEEE Power Engineering Review.