Taking a 660MW turbine generator shaft system as a target system, the torsional stresses responses are calculated under two-phase short-circuit fault by the finite element (FE) method which can obtain torsional stresses in local areas accurately. The results show that torsional stresses threaten the safety of shafts appear at the first several cycles of the vibration. And the amplitude of stress in weak cross sections located between the low pressure cylinder and the generator is much greater. In addition, the proportion of torsional stresses frequency components in different sections is distinct. The results are helpful to improve the safety management level of the unit.