Flicker characteristics of efficient lighting assessed by the IEC flickermeter

Abstract We present an experimental study of the behavior of modern lighting technologies under supply voltage fluctuations. Some studies have reported that flicker severity measurements could exceed the compatibility levels without leading to flicker complaints when modern lighting is in use. Such conclusions have resulted in two main proposals regarding the assessment of flicker: to relax the flicker compatibility indexes and to adapt standardized procedures to assess flicker based on a new reference lamp instead of the current reference, the incandescent lamp. Our work presents alternative tools for analyzing the effect of efficient lighting on the assessment of flicker. Our main findings challenge the assumption that efficient modern lighting is not sensitive to voltage fluctuations, at least over a considerable frequency range. Furthermore, the results oppose the use of the standardized functional model of the incandescent lamp for assessing the flicker severity produced by modern lamps.

[1]  A. Testa,et al.  A new simplified model of compact fluorescent lamps in the scenario of smart grids , 2012, 2012 IEEE 15th International Conference on Harmonics and Quality of Power.

[2]  J.F.G. Cobben,et al.  IMPROVING WEIGHTING FILTER OF UIE/IEC FLICKERMETER - BUILDING THE LAMP MODEL , 2007 .

[3]  Krzyszt Chmielowiec Flicker effect of different types of light sources , 2011, 11th International Conference on Electrical Power Quality and Utilisation.

[4]  A. Testa,et al.  IEEE Recommended Practice— Adoption of IEC 61000-4-15:2010, Electromagnetic compatibility (EMC)—Testing and measurement techniques—Flickermeter— Functional and design specifications , 2011 .

[5]  J. J. Mesas,et al.  Parameter estimation procedures for compact fluorescent lamps with electronic ballasts , 2013 .

[6]  Wil L. Kling,et al.  Flicker responses of different lamp types , 2009 .

[7]  D. Arlt,et al.  Examples of international flicker requirements in high voltage networks and real world measurements , 2007, 2007 9th International Conference on Electrical Power Quality and Utilisation.

[8]  M.H. Rashid,et al.  An overview of the modern light dimmer: design, operation, and application , 2005, Proceedings of the 37th Annual North American Power Symposium, 2005..

[9]  Carmine Landi,et al.  Design and Calibration of an Objective Flickermeter , 2006, IEEE Transactions on Instrumentation and Measurement.

[10]  J. J. Mesas,et al.  Model of discharge lamps with magnetic ballast , 2013 .

[11]  Julia Kowalski,et al.  Lighting the way: Perspectives on the global lighting market , 2012 .

[12]  I. Azcarate,et al.  Sensitivity to flicker of dimmable and non-dimmable lamps , 2012, 2012 IEEE International Instrumentation and Measurement Technology Conference Proceedings.

[13]  K. Redondo,et al.  Type testing of a highly accurate illuminance flickermeter , 2012, 2012 IEEE 15th International Conference on Harmonics and Quality of Power.

[14]  J. Drapela,et al.  Interharmonic - Flicker Curves of Lamps and Compatibility Lever for Interharmonic Voltages , 2007, 2007 IEEE Lausanne Power Tech.