Laboratory Testing of a Utility-Scale PV Inverter’s Operational Response to Grid Disturbances

This paper provides experimental results of a utility-scale (500 kW) solar PV inverter during simulated grid disturbances. This device was tested using simulations of system voltage during three different disturbances; simulated distribution and transmission faults, and voltage records that were collected during the Blue Cut Fire Event. The methods used for testing the three different scenarios of grid disturbances are detailed and the test setup is described. Additionally, the test results for each of the grid events are provided and an analysis of the test results is given. The test results show that the tested PV inverter’s response to grid disturbances depends in part on the fault-induced phase shift and harmonic content of the system voltage. These factors can impact the inverters ability to accurately calculate system frequency and can cause erroneous tripping on miscalculated frequency. The information provided in this paper can inform utilities, manufacturers, developers, and system planners of the potential performance of solar PV inverters during grid events.

[1]  Matthew Rylander,et al.  Derivation of WECC distributed PV system model parameters from quasi-static time-series distribution system simulations , 2017, 2017 IEEE Power & Energy Society General Meeting.

[2]  Barry Mather,et al.  Distribution-connected PV's response to voltage sags at transmission-scale , 2016, 2016 IEEE 43rd Photovoltaic Specialists Conference (PVSC).