Influence of sorption isotherm hysteresis effect on indoor climate and energy demand for heating

Abstract In order to investigate the effects of sorption isotherm hysteresis on indoor climate and energy demand, a new module for precise representation of mass transfer in materials in contact with indoor air, called Humi-mur, was developed and implemented in the energy performance simulation tool, TRNSYS. This extended whole-building HAM (Heat–Air–Moisture) simulation tool was then used to investigate the impact of the moisture-buffering effect on indoor conditions in a room. Two modelling approaches were compared: including/excluding moisture-buffering effect and including/excluding hysteresis in sorption isotherm. In addition, two ventilation strategies were used: constant airflow ventilation (CAV) and relative humidity sensitive ventilation (RHS). The simulation showed that for the CAV system, the use of moisture-buffering materials did not change energy demand but improved the indoor conditions. For the RHS ventilation system, the use of the buffering materials led to a higher energy demand, but the indoor relative humidity comfort was significantly improved. The results also showed that hysteresis of the sorption isotherm impacts on indoor conditions, even if the effect is smaller for the studied material than the average moisture-buffering effect.

[1]  J. Kurnitski,et al.  The effects of ventilation systems and building fabric on the stability of indoor temperature and humidity in Finnish detached houses , 2009 .

[2]  Ocg Olaf Adan,et al.  On the fungal defacement of interior finishes , 1994 .

[3]  K. Hasegawa,et al.  Moisture buffering and effect of ventilation rate and volume rate of hygrothermal materials in a single room under steady state exterior conditions , 2009 .

[4]  Björn Johannesson,et al.  A two-phase moisture transport model accounting for sorption hysteresis in layered porous building constructions , 2009 .

[5]  Jon Hand,et al.  CONTRASTING THE CAPABILITIES OF BUILDING ENERGY PERFORMANCE SIMULATION PROGRAMS , 2008 .

[6]  Monika Woloszyn,et al.  Modelling of hysteresis influence on mass transfer in building materials , 2009 .

[7]  Jaakko Paasi,et al.  Performance of ESD protective materials at low relative humidity , 2001 .

[8]  Povl Ole Fanger,et al.  Limiting criteria for human exposure to low humidity indoors , 2002 .

[9]  Lars Damkilde,et al.  A hysteresis model suitable for numerical simulation of moisture content in wood , 2007 .

[10]  J. Pieters,et al.  Influence of condensation and evaporation on the greenhouse climate and its regulation , 1997 .

[11]  Baizhan Li,et al.  Occupants' adaptive responses and perception of thermal environment in naturally conditioned university classrooms , 2010 .

[12]  G. W. Brundrett,et al.  A review of the factors influencing electrostatic shocks in the offices , 1977 .

[13]  Arnold Janssens,et al.  Experimental validation and sensitivity analysis of a coupled BES—HAM model , 2010 .

[14]  Désirée Gavhed,et al.  Perceived problems and discomfort at low air humidity among office workers , 2005 .

[15]  Jarl-Gunnar Salin,et al.  Inclusion of the sorption hysteresis phenomenon in future drying models: Some basic considerations , 2011 .

[16]  Marijke Steeman,et al.  Performance evaluation of indirect evaporative cooling using whole-building hygrothermal simulations , 2009 .

[17]  Monika Woloszyn,et al.  The effect of combining a relative-humidity-sensitive ventilation system with the moisture-buffering capacity of materials on indoor climate and energy efficiency of buildings , 2009 .

[18]  Peder Wolkoff,et al.  The dichotomy of relative humidity on indoor air quality. , 2007, Environment international.

[19]  Arnold Janssens,et al.  Effect of moisture inertia models on the predicted indoor humidity in a room , 2005 .

[20]  Toke Rammer Nielsen,et al.  Energy efficient demand controlled ventilation in single family houses , 2010 .

[21]  B. Hart Life cycle and reproduction of house‐dust mites: environmental factors influencing mite populations , 1998, Allergy.

[22]  Monika Woloszyn,et al.  Tools for performance simulation of heat, air and moisture conditions of whole buildings , 2008 .