Study on the Performance Characteristics of the Roof Mounted Electrical Air Conditioning System Using Inverter Scroll Compressor
暂无分享,去创建一个
Abstract The objective of this study is to investigate the cooling performance of the roof mounted air-conditioning system using electric driven scroll compressor for zero emission vehicles. This air conditioner with air source was used R-134a as a refrigerant and tested under various operating conditions such as refrigerant charge amount and indoor temperature, and compressor frequencies. Experimental results revealed that at all tested compressor frequencies, heat transfer rate of the evaporator increased and the cooling COP increased with the indoor temperature. In addition, the heat transfer rate of the evaporator was over 25.0kW sufficient for the cooling loads of an electric bus. Key Words : Cooling capacity, COP, Compressor work, Heat pump, R-134a 본 논문은 지식경제부에서 지원하는 산업원천기술개발사업의 일환으로 수행되었음 . * 교신저자 : 이동연(dylee@ynu.ac.kr)접수일 11년 08월 23일 수정일 11년 09월 22일 게재확정일 11년 10월 06일 기호설명 COP : 성능 (coefficient of performance) Hz : 주파수 (frequency) i : 엔탈피, (kJ/kg) . m : 질량유량 (kg/h) Q & : 열전달률, (W)