Electrical breakdown in high-voltage winding insulations of different manufacturing qualities

Due to an increasing demand for new, or the refurbishment of power stations, high-voltage rotating machines continue to play a significant role in generating electrical energy. An important component of these machines is their electrical insulation. Although much research has been done to improve the material, about a quarter of all failures still are related to insulation problems. Research to improve winding insulation is very complex because a large number of factors influence insulation life, among them the raw materials, size of the mica tapes, geometrical characteristics of the bar and taping- or manufacturing techniques. The results show that electrical tree propagation is the main electrical degradation mechanism that leads to breakdown of the main wall insulation and that poor impregnation of the insulation and type of taping can reduce time to breakdown significantly.

[1]  M. Kaufhold,et al.  Interface phenomena in stator winding insulation - challenges in design, diagnosis, and service experience , 2002 .

[2]  Tilman Weiers,et al.  The impact of low amplitude 100 Hz vibrations on the winding insulation of rotating high voltage machines; 15th International symposium on high voltage engineering ; ; Book of abstracts / 15th International Symposium on High Voltage Engineering , 2007 .

[3]  Yoshiharu Kaneda,et al.  The role of microscopic defects in multistress aging of micaceous insulation , 1995 .

[4]  K. Fröhlich,et al.  Effect of electrical tree propagation on breakdown in mica insulations , 2003 .

[5]  G. Stone,et al.  Electrical Insulation for Rotating Machines , 2003 .

[6]  G. C. Stone The statistics of aging models and practical reality , 1993 .

[7]  Ruben Vogelsang,et al.  Time to breakdown of high voltage winding insulations with respect to microscopic properties and manufaturing qualities , 2004 .

[8]  Y. Inoue,et al.  Statistical Analysis on the Electrical Failure Properties of the Form-Wound Epoxy Micaceous Insulation Systems for Rotating Machines , 1977, IEEE Transactions on Electrical Insulation.

[9]  S. Zoledziowski,et al.  Void formation and electrical breakdown in epoxy resin , 1977, IEEE Transactions on Power Apparatus and Systems.

[10]  John C. Fothergill,et al.  Electrical degradation and breakdown in polymers , 1992 .

[11]  W. McDermid Damage resulting from long term slot discharge activity in a hydrogen environment , 1990, IEEE International Symposium on Electrical Insulation.

[12]  Hee-Dong Kim,et al.  Effect of aging on the microstructure evolution, thermal and mechanical properties of mica/epoxy composite , 1999, 1999 Annual Report Conference on Electrical Insulation and Dielectric Phenomena (Cat. No.99CH36319).

[13]  Ronald William Sillars Electrical insulating materials and their application , 1981 .

[14]  J. H. Mason Assessing the resistance of polymers to electrical treeing , 1981 .

[15]  Chanan Singh,et al.  Report of Large Motor Reliability Survey of Industrial and Commercial Installations, Part II , 1985, IEEE Transactions on Industry Applications.

[16]  M. Dalva,et al.  A survey of faults on induction motors in offshore oil industry, petrochemical industry, gas terminals and oil refineries , 1994, Proceedings of IEEE Petroleum and Chemical Industry Technical Conference (PCIC '94).

[17]  H. Mitsui,et al.  Statistical analysis on the electrical failure properties of the form-wound insulation systems for rotating machines , 1976, 1976 IEEE International Conference on Electrical Insulation.