A comparative study of DFT and Moving Window Averaging technique of current differential protection on Transmission line

This paper is based on the study of current differential protection scheme on transmission line by using Moving Window Averaging technique and Discrete Fourier Transform. From the beginning of the history of power system, researchers have tried to increase the speed and sensitivity of transmission line protection in the power system protection field without compromising the security. Current differential protection scheme always provides sensitive protection with sharp discrimination of the disturbance area from the protection zone. Current differential protection scheme is immune to power swings and load encroachment. In the first method DFT, we can easily measure the phasors of the two ends of the transmission line which is very much essential for power system. With the help of moving window averaging technique extraction of the dc component of the current of transmission line is possible from both the sending and receiving ends. It is shown that under steady state condition, the differential current is zero while an internal line fault leads to non-zero differential current. The transmission line model is simulated with the help of PSCAD software.

[1]  T.T. Nguyen,et al.  A fast and accurate method for estimating power systems phasors using DFT with interpolation , 2006, 2006 IEEE Power Engineering Society General Meeting.

[2]  Shan C. Sun,et al.  A Current Differential Relay System Using Fiber Optics Communications , 1983, IEEE Transactions on Power Apparatus and Systems.

[3]  P. A. Crossley,et al.  A new type of differential feeder protection relay using the Global Positioning System for data synchronization , 1997 .

[4]  G. Benmouyal,et al.  Removal of DC-offset in current waveforms using digital mimic filtering , 1995 .

[5]  Y. Kang,et al.  Fourier Transform-Based Modified Phasor Estimation Method Immune to the Effect of the DC Offsets , 2009, IEEE Transactions on Power Delivery.

[6]  James S. Thorp,et al.  Computer Relaying for Power Systems , 2009 .

[7]  M.C. Chandorkar,et al.  Current Differential Protection of Transmission Line Using the Moving Window Averaging Technique , 2010, IEEE Transactions on Power Delivery.

[8]  Q.X. Yang,et al.  A Current Differential Relay for a 1000-kV UHV Transmission Line , 2007, IEEE Transactions on Power Delivery.

[9]  Chi-Kong Wong,et al.  Novel wavelet approach to current differential pilot relay protection , 2003, 2003 IEEE Power Engineering Society General Meeting (IEEE Cat. No.03CH37491).

[10]  Aboelmagd Noureldin,et al.  Fast orthogonal search approach for distance protection of transmission lines , 2010 .

[11]  James S. Thorp,et al.  Charge comparison protection of transmission lines-relaying concepts , 1992 .

[12]  S. A. Soman,et al.  Current Differential Protection of Transmission Line Using the Moving Window Averaging Technique , 2010 .