Transcritical CO2 refrigeration cycle with ejector-expansion device
暂无分享,去创建一个
An ejector expansion transcritical CO2 refrigeration cycle is proposed to improve the COP of the basic transcritical CO2 cycle by reducing the expansion process losses. A constant pressure mixing model for the ejector was established to perform the thermodynamic analysis of the ejector expansion transcritical CO2 cycle. The effect of the entrainment ratio and the pressure drop in the receiving section of the ejector on the relative performance of the ejector expansion transcritical CO2 cycle was investigated for typical air conditioning operation conditions. The effect of different operating conditions on the relative performance of the ejector expansion transcritical CO2 cycle was also investigated using assumed values for the entrainment ratio and pressure drop in the receiving section of the ejector. It was found that the COP of the ejector expansion transcritical CO2 cycle can be improved by more than 16% over the basic transcritical CO2 cycle for typical air conditioning operation conditions.
[1] W. E. Kraus,et al. Expander-compressor for a more efficient use of CO2 as refrigerant , 1998 .
[2] Alan A. Kornhauser,et al. The Use of an Ejector as a Refrigerant Expander , 1990 .
[3] Eckhard A. Groll,et al. Efficiencies of transcritical CO2 cycles with and without an expansion turbine , 1998 .
[4] Piotr A. Domanski,et al. Evaluation of Carbon Dioxide as R-22 Substitute for Residential Air-Conditioning. | NIST , 2002 .