고발열 전자장치의 액체냉각 방식에 관한 실험연구
暂无分享,去创建一个
Experiments have been performed to investigate the cooling characteristics of the indirect liquid cooling method using water. The parameters were 9.8, 19.9 and 30.4 W/㎠ for heat flux of the simulated VLSI chips and Reynolds numbers ranging from approximately 5,000 to 16,000. The test section was consisted with in-line, four-row array of 12 heat sources for simulating 4×3 multichip module which were flush mounted on the top wall of a horizontal, rectangular channel of aspect ratio 0.2. The inlet temperature was 18.4 ℃ for all experiments, and the heater surface temperature did not exceed 80 ℃. The heat transfer coefficient can be considered to have reached a row-number-independent, fully developed value by the third row for all test runs. The average Nusselt numbers for the rows of the array decreased by approximately 15 % from the first to the fourth row, and the data for the first row were in good agreement within 8 % with results obtained by Incropera et al.