Measurement of Power System Subsynchronous Driving Point Impedance and Comparison with Computer Simulations

An integral part of a subsynchronous resonance analysis is the frequency scan of digital computer models of the network connected to the machines under study to estimate the equivalent driving point impedance over the frequency range of interest (10 to 50 Hz normally). Until now, the limited amount of correlation that exists between frequency scan simulations and test measurements has been of a rather indirect nature, using the installed and operating study machines. This paper presents a technique to extract the subsynchronous positive sequence driving point impedance in relation to frequency of an operating power system from a staged phase-to-phase fault. No external source of excitation is required. Field test results are presented for the B.C. Hydro system and are compared to frequency scans of corresponding system models to verify the adequacy of the models.

[1]  G. D. Bergland,et al.  A guided tour of the fast Fourier transform , 1969, IEEE Spectrum.

[2]  P. Kundur,et al.  Accurate Calculation of Asymmetrical Fault Currents in Comples Power Systems , 1981, IEEE Transactions on Power Apparatus and Systems.

[3]  Daniel Crevier,et al.  Estimation of Higher Frequency Network Equivalent Impedances by Harmonic Analysis Natural Waveforms , 1978, IEEE Transactions on Power Apparatus and Systems.

[4]  R.G. Farmer,et al.  Use of Frequency Scanning Techniques for Subsynchronous Resonance Analysis , 1979, IEEE Transactions on Power Apparatus and Systems.

[5]  D.G. Ramey,et al.  Simplified transmission and generation system analysis procedures for subsynchronous resonance problems , 1977, IEEE Transactions on Power Apparatus and Systems.

[6]  D.G. Ramey,et al.  Subsynchronous Resonance Tests and Torsional Monitoring System Verification at the Cholla Station , 1980, IEEE Transactions on Power Apparatus and Systems.

[7]  L. Hannett,et al.  Determination of Synchronous Machine Electrical Characteristics by Test , 1983, IEEE Transactions on Power Apparatus and Systems.

[8]  J. Chow,et al.  HVDC-AC Harmonic Interaction Part I - Development of a Harmonic Measurement System Hardware and Software , 1982, IEEE Transactions on Power Apparatus and Systems.

[9]  S. Abe,et al.  Measurements of Synchronous Machine Parameters Under Operating Condition , 1982, IEEE Transactions on Power Apparatus and Systems.

[10]  Gerald Manchur,et al.  Generator Models Established by Frequency Response Tests on a 555 MVA Machine , 1972 .