Measurement of the Individual Harmonics Reactive Power in Nonsinusoidal Systems

This paper presents a method of individual harmonics reactive power measurement for a load supplied by a nonsinusoidal source. The method consists of transforming the load-voltage and the load-current frequency spectra by multiplying both quantities by the quadrature voltages. Next, the products obtained are filtered with a pair of mutually symmetrical narrow-band filters. The mean value of the filter output voltage product appears to be proportional to the individual harmonics reactive power of the load.

[1]  Leszek S. Czarnecki,et al.  Minimisation of distortion power of nonsinusoidal sources applied to linear loads , 1981 .

[2]  L. S. Czarnecki Measurement principle of a reactive power meter for nonsinusoidal systems , 1981, IEEE Transactions on Instrumentation and Measurement.