Measurements of free-burning arc in the power network were recorded at 22 kV busbar voltage transformer. As the measuring transformer distort the record, it was not possible to determine the response by measurements. The experiment was therefore modeled using EMTP -ATP. In addition to the described model of measuring voltage transformer, it has been modeled the network in which the measurement takes place. In order to analyze time-varying oscillatory character of voltage response two kind of time-frequency signal processing method were proposed: those which characterize time behavior of the waveform, and those which give information about frequency components. Obtained representations are based on classical Fourier spectrum and time-frequency representations: Smoothed Pseudo-Wigner-Ville Distribution and the S-transform.
[1]
Lalu Mansinha,et al.
Localization of the complex spectrum: the S transform
,
1996,
IEEE Trans. Signal Process..
[2]
Irene Yu-Hua Gu,et al.
Signal processing of power quality disturbances
,
2006
.
[3]
F. Hlawatsch,et al.
Linear and quadratic time-frequency signal representations
,
1992,
IEEE Signal Processing Magazine.
[4]
Tadeusz Lobos,et al.
Time–Frequency Analysis of Complex Space Phasor in Power Electronics
,
2004,
IEEE Transactions on Instrumentation and Measurement.
[5]
M. Grady,et al.
Power quality indices for transient disturbances
,
2006,
2006 IEEE Power Engineering Society General Meeting.