Single-phase 50-kW 16.7-Hz four-quadrant line-side converter for railway traction application
暂无分享,去创建一个
Railway grid interaction is a major concern when developing the power chain of a railway traction vehicle and its control. Especially line-current harmonics and grid stability have to be considered. Developing an optimised control scheme for the four-quadrant line-side converter of a railway traction vehicle operating at the 15-kV, 16.7-Hz grid requires advanced simulation tools, combined with suitable laboratory experiments for verification. This paper describes the simulation concept, the control structure, the realisation of a four-quadrant line-side converter test bench and measurement results for stationary and dynamic behaviour, verifying excellent operation.
[1] William H. Press,et al. Numerical recipes in C , 2002 .
[2] V. Staudt,et al. Single-phase 50-kW, 16.7-Hz railway-grid representation featuring variable grid parameters , 2008, 2008 IEEE Power Electronics Specialists Conference.