Cost effective multi-pulse transformer solutions for harmonic mitigation in AC drives

More and more AC drive installations are requiring manufacturer's to improve line side harmonics to ultimately meet IEEE Harmonic Std 519-1992 on site. This paper reveals several patented transformer topologies for such an effort. Compared with other harmonic solutions, auto and isolated transformers possess advantages as being simple, reliable, minimal line resonance problems and relatively cost effective. The proposed nine and twelve-phase auto-transformers can be viewed as a polygon winding type, where besides achieving an improved input current harmonics, junction points among various windings along the polygon can be wired out for step-down, unity and step-up voltage transfers. When electrically isolated primary windings are added, unlimited transfer ratio is available for every application. Application of these new industrial transformer devices, along with simple power diode energy conversion methods, result in a robust and reliable system that provides good DC bus regulation for AC drives utilizing a common DC bus configuration. The proposed topologies also provide a high AC input power factor and minimize harmonic currents to the utility interface. The paper provides technical analysis and field site data on the new topologies, as well as per unit metric comparison to other harmonic mitigation techniques versus horsepower size.

[1]  J. M. Frank Origin, development, and design of K-factor transformers , 1997 .

[2]  Tomotsugu Kubota,et al.  Voltage-phase shifting effect of three-phase harmonic canceling reactors and their applications to three-level diode rectifiers , 1999, Conference Record of the 1999 IEEE Industry Applications Conference. Thirty-Forth IAS Annual Meeting (Cat. No.99CH36370).

[3]  F. Peng Harmonic sources and filtering approaches , 2001 .

[4]  P.N. Enjeti,et al.  Auto-connected electronic transformer (ACET) based multi-pulse rectifiers for utility interface of power electronic systems , 1998, Conference Record of 1998 IEEE Industry Applications Conference. Thirty-Third IAS Annual Meeting (Cat. No.98CH36242).

[5]  R. G. Ellis Harmonic analysis of industrial power systems , 1994 .

[6]  R. Ellis Harmonic analysis of industrial power systems , 1994, Proceedings of IEEE Pulp and Paper Industry Conference.

[7]  J. P. Rhode,et al.  Transformer derating for harmonic currents: a wideband measurement approach for energized transformers , 1995, IAS '95. Conference Record of the 1995 IEEE Industry Applications Conference Thirtieth IAS Annual Meeting.

[8]  Derek A. Paice,et al.  Power Electronic Converter Harmonics: Multipulse Methods for Clean Power , 1995 .

[9]  J. Salmon,et al.  An asymmetrical half-bridge active DC filter for industrial drive systems using multipulse utility rectifiers with harmonic reducing input transformers , 2003, IEEE International Electric Machines and Drives Conference, 2003. IEMDC'03..

[10]  德里克·艾伯特·佩斯 Optimized 18-pulse type AC/DC, or DC/AC, converter system , 1991 .

[11]  M. F. McGranaghan,et al.  Designing harmonic filters for adjustable speed drives to comply with IEEE-519 harmonic limits , 1997, 1997 Rural Electric Power Conference (Cat. No.97CH36079).