Partial discharge initiated by free moving metallic particles on GIS insulator surface: severity diagnosis and assessment

Free moving metallic particles are one of the most common defects leading to insulation failures in gas insulated substation (GIS) equipment. The present research is designed to diagnose and assess the severity levels of partial discharge (PD) initiated by free moving metallic particles on GIS insulator surface. On a well-established 252 kV GIS experiment platform, long term tests were conducted to observe the entire development process of partial discharge from its very initiation stage till eventual flashover as the applied voltage gradually boosted. Real time measurement was undertaken during the tests to capture the trend curve of partial discharge as a result of test time, scatter plot, histogram, grey-scale map, and time-frequency map of partial discharge. The experimental results indicate that 1) partial discharge provoked by free moving metallic particles in GIS goes through three severity levels, namely, minor discharge, moderate discharge, and threatening discharge; 2) as partial discharge develops, the phase distribution is widening and corresponding shape changes occur in the scatter plot, histogram, grey-scale map, and time-frequency map. It is recommended that the features of phase distribution and the corresponding spectra could be used as important criteria in diagnosing and assessing the severity levels of partial discharge initiated by free moving metallic particles on GIS insulator surface.

[1]  R. Baumgartner,et al.  Partial discharge. X. PD in gas-insulated substations-measurement and practical considerations , 1992, IEEE Electrical Insulation Magazine.

[2]  H. Aoyagi,et al.  A study on effects of conducting particles in SF/sub 6/ gas and test methods for GIS , 1988 .

[3]  M. M. Morcos,et al.  Insulation integrity of GIS/GITL systems and management of particle contamination , 2000 .

[4]  P. Bolin,et al.  Introduction and applications of gas insulated substation (GIS) , 2005, IEEE Power Engineering Society General Meeting, 2005.

[5]  Jin Li EXAMINATION AND RESEARCH ON THE PARTIAL DISCHARGE OF METALLIC PARTICLES IN GIS , 2002 .

[6]  Martin D. Judd,et al.  Partial discharge diagnostics for gas insulated substations , 1995 .

[7]  H. Okubo,et al.  Detection of harmful metallic particles inside gas insulated switchgear using UHF sensor , 2008, IEEE Transactions on Dielectrics and Electrical Insulation.

[8]  J. Amarnath,et al.  Behavior of metallic particles in a single phase gas insulated system with dielectric coated electrodes , 2008, 2008 International Conference on Condition Monitoring and Diagnosis.

[9]  W. Boeck Insulation Co-Ordination of GIS, Return of Experience, On Site Tests and Diagnostic Techniques , 1998 .

[10]  J. B. Kim,et al.  Development of monitoring and diagnostic system for SF/sub 6/ gas insulated switchgear , 2002, Conference Record of the the 2002 IEEE International Symposium on Electrical Insulation (Cat. No.02CH37316).

[11]  L. Niemeyer,et al.  The importance of statistical characteristics of partial discharge data , 1992 .