The research of DC capacitance voltages balancing strategy based on cascade STATCOM using individual phase instantaneous current tracking

Due to the shunt loss, switching loss and pulse delay, the DC capacitors voltage of cascade STATCOM can't maintain balanced which would influence the output voltage harmonics and even its normal operation. A novel DC capacitors voltage balancing control strategy based on individual phase instantaneous current tracking is proposed in this paper, the active power is properly distributed among the H-bridge units in the same phase to achieve the balance of DC capacitors voltage, and it is theoretically proved that the method is suitable for various condition while won't change the fundamental component of output voltage. The correctness and effectiveness of the method are validated by MATLAB simulation.

[1]  Fang Zheng Peng,et al.  A multilevel voltage-source inverter with separate DC sources for static VAr generation , 1995, IAS '95. Conference Record of the 1995 IEEE Industry Applications Conference Thirtieth IAS Annual Meeting.

[2]  H. L. Thanawala,et al.  Assessment of two different STATCOM configurations for FACTS application in power systems , 1998, POWERCON '98. 1998 International Conference on Power System Technology. Proceedings (Cat. No.98EX151).

[3]  Gregory F. Reed,et al.  STATCOM application at VELCO Essex substation , 2001, 2001 IEEE/PES Transmission and Distribution Conference and Exposition. Developing New Perspectives (Cat. No.01CH37294).

[4]  L. Xu,et al.  Advanced SVC control for damping power system oscillations , 1991 .

[5]  Yuan-Yih Hsu,et al.  Damping of generator oscillations using an adaptive static VAR compensator , 1992 .

[6]  L.A.S. Pilotto,et al.  Thyristor-Controlled Reactors Nonlinear and Linear Dynamic Analytical Models , 2008, IEEE Transactions on Power Delivery.

[7]  J. Svensson,et al.  Dynamic Performance Comparison of Synchronous Condenser and SVC , 2008, IEEE Transactions on Power Delivery.

[8]  Luis Marroyo,et al.  Individual Voltage Balancing Strategy for PWM Cascaded H-Bridge Converter-Based STATCOM , 2008, IEEE Transactions on Industrial Electronics.

[9]  S. Bowes New sinusoidal pulsewidth-modulated invertor , 1975 .

[10]  Geng Jun-cheng BALANCING CONTROL OF DC VOLTAGES OF 50MVA STATCOM BASED ON CASCADE MULTILEVEL INVERTERS , 2004 .

[11]  D. Soto,et al.  Decoupled control of capacitor voltages in a PWM cascade StatCom , 2008, 2008 IEEE Power Electronics Specialists Conference.

[12]  H. Akagi,et al.  Control and Performance of a Medium-Voltage Transformerless Cascade PWM STATCOM with Star-Configuration , 2006, Conference Record of the 2006 IEEE Industry Applications Conference Forty-First IAS Annual Meeting.

[13]  M. L. Woodhouse,et al.  Type testing of the GTO valves for a novel STATCOM convertor , 2001 .

[14]  I. Bonfanti,et al.  Design and operational testing on thyristor modules for the SVC Kemps Creek , 1990 .

[15]  D. J. Adams,et al.  A power line conditioner using cascade multilevel inverters for distribution systems , 1997, IAS '97. Conference Record of the 1997 IEEE Industry Applications Conference Thirty-Second IAS Annual Meeting.