Experimental investigation on heat and mass transfer in heating tower solution regeneration using packing tower

Abstract Heating towers which can take advantage of energy from air for heating supply is drawing more and more attention. However, the solution dilution problem exists in both open-type and closed-type heating towers, resulting an increasing risk of system freeze. This paper presents an alternative way for heating tower solution regeneration based on packed beds. A cross-flow regenerator equipped with PVC structured packing was established and glycol aqueous solution was selected as the circulating fluid. The effects of the inlet parameters on moisture removal rate, humidity effectiveness and thermal efficiency are experimentally investigated. Correlation expressions of heat and mass transfer coefficients are also proposed, which can be primary parameters for simulation and optimization. Besides, performance comparation between heating tower solution regeneration and liquid desiccant regeneration available in the literature is figured out. The results indicate that the impacts of inlet parameters show similar tendency with those in liquid desiccant regeneration. While the regeneration temperature required in heating tower is much lower than that in liquid desiccant regeneration, due to the lower required solution equivalent humidity ratio and regenerated air humidity ratio. That makes it possible to utilize low-grade energy.

[1]  Ioan Sarbu,et al.  General review of ground-source heat pump systems for heating and cooling of buildings , 2014 .

[2]  Xiaosong Zhang,et al.  Experimental study of heat and mass transfer characteristics in a cross-flow heating tower , 2017 .

[3]  Herbert W. Stanford HVAC Water Chillers and Cooling Towers: Fundamentals, Application, and Operation , 2003 .

[4]  Sm Deng,et al.  Developing a new frosting map to guide defrosting control for air-source heat pump units , 2015 .

[5]  Xiaohua Liu,et al.  Effect of regeneration mode on the performance of liquid desiccant packed bed regenerator , 2009 .

[6]  Xiaosong Zhang,et al.  Experimental study on dehumidifier and regenerator of liquid desiccant cooling air conditioning system , 2007 .

[7]  C. Liang,et al.  Performance analysis and experimental study of heat-source tower solution regeneration , 2014 .

[8]  Xiaohua Liu,et al.  Experimental investigation of the heat and mass transfer between air and liquid desiccant in a cross-flow regenerator , 2007 .

[9]  Nianping Li,et al.  Study of Heat-source-Tower Heat Pump System Efficiency☆ , 2015 .

[10]  Guangcai Gong,et al.  Research on frost formation in air source heat pump at cold-moist conditions in central-south China , 2013 .

[11]  Donggen Peng,et al.  Feasibility and performance analysis of a desiccant solution regenerator using hot air , 2011 .

[12]  Zhang Xiaosong,et al.  Construction and experimental research on heat pump system based on heat-source tower , 2010 .

[13]  Quan Zhang,et al.  Experimental Investigation of the Performance of a Reversibly Used Cooling Tower Heating System Using Heat Pump in Winter , 2011, 2011 Asia-Pacific Power and Energy Engineering Conference.

[14]  Zhang Xiaosong Energy-saving analysis of solution regeneration in heat-source tower based on recovery of air energy , 2011 .

[15]  Quan Zhang,et al.  Calculations on performance characteristics of counterflow reversibly used cooling towers , 2012 .

[16]  Meysam Soleymani,et al.  Simplified analysis of heat and mass transfer model in liquid desiccant regeneration process , 2010 .

[17]  Ahmed M. Hamed,et al.  The effect of inlet parameters on the performance of packed tower-regenerator , 2002 .

[18]  Xin Zhou,et al.  Field testing and performance analyses of ground source heat pump systems for residential applications in Hot Summer and Cold Winter area in China , 2016 .

[19]  Jianlin Cheng,et al.  Application Research on the Closed-loop Heat-source-Tower Heat Pump Air Conditioning System in Hot-summer and Cold-winter Zone , 2015 .

[20]  Nianping Li,et al.  Study on the dynamic and thermal performances of a reversibly used cooling tower with upward spraying , 2016 .

[21]  K. Y. Qu,et al.  Heat and mass transfer model of cross flow liquid desiccant air dehumidifier/regenerator , 2007 .

[22]  Chaobin Dang,et al.  Experimental analysis of mass transfer in adiabatic structured packing dehumidifier/regenerator with liquid desiccant , 2010 .

[23]  D. Goswami,et al.  Study of an aqueous lithium chloride desiccant system: air dehumidification and desiccant regeneration , 2002 .

[24]  Zhiwei Lian,et al.  Performance investigation on the ultrasonic atomization liquid desiccant regeneration system , 2016 .

[25]  Carey J. Simonson,et al.  Annual evaluation of energy, environmental and economic performances of a membrane liquid desiccant air conditioning system with/without ERV , 2014 .

[26]  Esam Elsarrag,et al.  Performance study on a structured packed liquid desiccant regenerator , 2006 .

[27]  Andrea Gasparella,et al.  Experimental analysis on desiccant regeneration in a packed column with structured and random packing , 2009 .

[28]  Long D. Nghiem,et al.  Using electrodialysis for regeneration of aqueous lithium chloride solution in liquid desiccant air conditioning systems , 2016 .

[29]  T. Fujita,et al.  Thermal Characteristics of Heating Towers , 2012 .

[30]  Shiming Deng,et al.  A method for evaluating the heat and mass transfer characteristics in a reversibly used water cooling tower (RUWCT) for heat recovery , 2002 .

[31]  Yu Wang,et al.  Artificial neural network analysis of the performance characteristics of a reversibly used cooling tower under cross flow conditions for heat pump heating system in winter , 2011 .

[32]  Xuelai Zhang,et al.  Experimental investigation on a new method of regenerating dehumidification solution–release solution droplet into vacuum , 2013 .

[33]  Wang Lijie,et al.  Experimental Study on Energy Efficiency of Heat-source Tower Heat Pump Units in Winter Condition , 2011, 2011 Third International Conference on Measuring Technology and Mechatronics Automation.

[34]  Xiaohua Liu,et al.  Coupled heat and mass transfer characteristic in packed bed dehumidifier/regenerator using liquid desiccant , 2008 .

[35]  C. Liang,et al.  Experimental study on heat transfer coefficient between air and liquid in the cross-flow heat-source tower , 2012 .

[36]  T. Fujita,et al.  Vapor Pressure of Aqueous Solutions of Ethylene Glycol , 1989 .

[37]  Carey J. Simonson,et al.  State-of-the-art in liquid desiccant air conditioning equipment and systems , 2016 .

[38]  Z. Xiaolin Mass transfer characteristics in heat-source tower , 2011 .

[39]  Qing Yang,et al.  Photovoltaic capacitive deionization regeneration method for liquid desiccant cooling system , 2017 .