Comments on draft ANSI S12.2, American National standard on criteria for evaluating room noise
暂无分享,去创建一个
In 1995, American National Standard S12.2‐1995 on room noise criteria was issued. Two methods for specifying and evaluating room noise were presented, the NCB noise‐criterion curves [J. Acoust. Soc. Am. 86, 650–664 (1989)] and the RC curves [Noise Control Eng. J. 45, 243–250 (1997)]. The NCB curves were derived from the characteristics of hearing with emphasis on speech interference level and loudness level, while the RC curves were derived from experimental studies in offices where the HVAC noise was low enough that there were no complaints from room occupants. The NCB curves were applicable to rooms ranging from concert halls to factory spaces, while the RC curves were largely restricted to office, hospital, and residential spaces. The two sets were incompatible at low frequencies and low sound levels. The NCB curves assumed that the HVAC noise was free of surging and strong turbulence. The RC curves demanded lower levels at low frequencies, thus permitting some degree of surging and turbulence. The new...