Thermal Analysis of Compressible CO2 Flow for PFE TeSS Nozzle of Fire Detection System

A thermal analysis of the compressible CO2 flow for the Portable Fire Extinguisher (PFE) system has been performed. A SINDA/FLUINT model has been developed for this analysis. The model includes the PFE tank and the TeSS nozzle, and both have initial temperature of 72 F. In order to investigate the thermal effect on the nozzle due to discharging CO2, the PFE TeSS nozzle pipe has been divided into three segments. This model also includes heat transfer predictions for PFE tank inner and outer wall surfaces. The simulation results show that the CO2 discharge rates have fulfilled the minimum flow requirements that the PFE system discharges 3.0 Ibm CO2 in 10 seconds and 5.5 Ibm of CO2 in 45 seconds during its operation. At 45 seconds, the PFE tank wall temperature is 63 F, and the TeSS nozzle cover wall temperatures for the three segments are 47 F, 53 F and 37 F, respectively. Thermal insulation for personal protection is used for the first two segments of the TeSS nozzle. The simulation results also indicate that at 50 seconds, the remaining CO2 in the tank may be near the triple point (gas, liquid and solid) state and, therefore, restricts the flow.