Analysis on the dynamic responses of a prototype line from iced broken conductors

Abstract A full scale transmission line section of three continuous spans was established. With the consideration of the equivalent mass of the accreted ice, steel cables are used to simulate the iced conductors. For different types of conductors and ice thickness, broken conductor experiments were carried out. Under different broken cases, time histories of the tensions and displacements at the middle of conductor spans were measured. The first order damping coefficients of the line section for different broken cases were calculated. The Fourier transform of the experimental time history of the conductor tensions was completed. The dynamic impact factors of the conductor tensions were determined. The experimental results show that the impact effect is more significant for the location nearer to the break point. The dynamic impact factors decrease with the increase of the ice thickness, and the impact factors of conductors without accreted ice are much higher than those of conductors with accreted ice. With the increase of the ice thickness, the initial tensions before break as well as the ratios of the residual static tensions to the initial tensions increase. Nearly all the first peak tensions are close to the initial tensions for the broken cases with accreted ice. The damping coefficients determined by the experimental identification were applied to the finite element analysis (FEA) model. The stiffness of the accreted ice as well as the contact effect between the conductors and the ground are considered in the FEA model. The numerical simulations were performed for different broken cases. Both the residual static tensions and the first peak tensions by the numerical simulations were well agreed with the experimental values. The maximum differences are 5.6% and 12.9% respectively.

[1]  Jun Lee,et al.  Longitudinal Loads From Broken Conductors and Broken Insulators and Their Effect on Transmission Lines , 1980, IEEE Transactions on Power Apparatus and Systems.

[2]  Liang Zheng DYNAMIC RESPONSE OF TRANSMISSION TOWER WITH RUPTURED WIRES , 2007 .

[3]  Ghyslaine McClure,et al.  Modeling the EPRI-Wisconsin Power and Light Broken Wire Tests , 2010, IEEE Transactions on Power Delivery.

[4]  R. Clough,et al.  Dynamics Of Structures , 1975 .

[5]  John F. Fleming,et al.  Broken wire analysis of transmission line systems , 1984 .

[6]  William Wood,et al.  Broken Wire Tests on a Model Transmission Line System , 1981, IEEE Transactions on Power Apparatus and Systems.

[7]  K. Tucker,et al.  Numerical Model Validation and Sensitivity Study of a Transmission-Line Insulator Failure Using Full-Scale Test Data , 2007, IEEE Transactions on Power Delivery.

[8]  Jing Bo Yang,et al.  Analysis on the Dynamic Responses of the Broken Conductors in Transmission Lines , 2011 .

[9]  M. Farzaneh,et al.  Modelling the Dynamic Response of Iced Transmission Lines Subjected to Cable Rupture and Ice Shedding , 2013, IEEE Transactions on Power Delivery.

[10]  Ghyslaine McClure,et al.  Modeling the structural dynamic response of overhead transmission lines , 2003 .

[11]  Jorge Daniel Riera,et al.  Model uncertainty in the assessment of transmission line towers subjected to cable rupture , 2008 .

[12]  Jingbo Yang,et al.  Unbalanced tension analysis for UHV transmission towers in heavy icing areas , 2012 .

[13]  Alain H. Peyrot,et al.  Dynamic Response of Ruptured Conductors in Transmission Lines , 1982, IEEE Transactions on Power Apparatus and Systems.

[14]  Masoud Farzaneh,et al.  Numerical analysis of the dynamic effects of shock-load-induced ice shedding on overhead ground wires , 2007 .