Reliability Considerations in Systems Applications of Uninterruptible Power Supplies

A redundant static inverter is applied as an uninterruptible power supply (UPS). A reliability analysis is presented showing that the introduction of a static bypass transfer switch brings about a reliability improvement of 8.5 to 1 in the mean time between failure (MTBF). This gives MTBF greater than 600 000 h. The static bypass transfer switch provides a synchronized automatic transfer in less than 1 ms from the UPS to the normal ac input power source upon a failure of the UPS.

[1]  A. D. Patton,et al.  Power System Reliability I-Measures of Reliability and Methods of Calculation , 1964 .

[2]  W. H. Dickinson Report on reliability of electric equipment in industrial plants , 1962, Transactions of the American Institute of Electrical Engineers, Part II: Applications and Industry.

[3]  Edward W. Davis,et al.  Application ofInverter Drives , 1969 .

[4]  Edward W. Davis,et al.  Application of Inverter Drives , 1969 .