Transient Simulation and Analysis of Three-Phase Five-Limb Step-Up Transformer Following an Out-of-Phase Synchronization
暂无分享,去创建一个
Theoretical and experimental analyses are presented of the electromagnetic transient following the out-of-phase synchronization of a three-phase five-limb step-up transformer; this means an abnormal condition where the angle between phasors representing the generated voltages and those representing the power network voltages at the instant of closure of the connecting circuit breaker is not near zero, as normal, but may be as much as 180 degrees (phase opposition). When this happens, the peak values of the transient currents in the windings of the transformer might be sensibly higher than those of the failure currents estimated in a conventional way; in addition, they correspond to unbalanced magnetomotive forces (MMF) in the primary and secondary windings of each phase of the machine. The currents and fluxes during the transient are computed by a nonconventional circuital nonlinear model of the transformer simulated by the electromagnetic transient program (EMTP). The results of an experimental validation made on a specially built 100 kVA three-phase five-limb transformer are also reported. >
[1] E.P. Dick,et al. Transformer Models for Transient Studies Based on Field Measurements , 1981, IEEE Transactions on Power Apparatus and Systems.
[2] J. H. Provanzana,et al. Analysis of a generator step-up transformer failure following faulty synchronization , 1988 .
[3] G. R. Slemon,et al. Equivalent circuits for transformers and machines including non-linear effects , 1953 .
[4] E. C. Cherry. The Duality between Interlinked Electric and Magnetic Circuits and the Formation of Transformer Equivalent Circuits , 1949 .