Electrothermal Coordination in Cable Based Transmission Grids

Electrothermal coordination (ETC) is introduced for cable based transmission grids. ETC is the term covering operation and planning of transmission systems based on temperature, instead of current. ETC consists of one part covering the load conditions of the system and one covering the thermal behavior of the components. The dynamic temperature calculations of power cables are suggested to be based on thermoelectric equivalents (TEEs). It is shown that the thermal behavior can be built into widely used load flow software, creating a strong ETC tool. ETC is, through two case scenarios, proven to be beneficial for both operator and system planner. It is shown how the thermal behavior can be monitored in real-time during normal dynamic load and during emergencies. In that way, ETC enables cables to be loaded above their normal rating, while maintaining high reliability of the system, which potentially can result in large economic benefits.

[1]  G. J. Anders,et al.  Modelling of Dynamic Transmission Cable Temperature Considering Soil-Specific Heat, Thermal Resistivity, and Precipitation , 2013, IEEE Transactions on Power Delivery.

[2]  Faruk Aras,et al.  An Assessment of the Methods for Calculating Ampacity of Underground Power Cables , 2005 .

[3]  R. S. Olsen,et al.  Dynamic temperature estimation and real time emergency rating of transmission cables , 2012, 2012 IEEE Power and Energy Society General Meeting.

[4]  F.D. Galiana,et al.  Electrothermal coordination part I: theory and implementation schemes , 2005, IEEE Transactions on Power Systems.

[5]  A. Hiranandani,et al.  Calculation of Conductor Temperatures and Ampacities of Cable Systems Using a Generalized Finite Difference Model , 1991, IEEE Power Engineering Review.

[6]  J.G. Slootweg,et al.  Incorporating weather statistics in determining overhead line ampacity , 2005, 2005 International Conference on Future Power Systems.

[7]  G. Anders,et al.  Ampacity Reduction Factors for Cables Crossing Thermally Unfavorable Regions , 2001, IEEE Power Engineering Review.

[8]  George J. Anders,et al.  Rating of Electric Power Cables: Ampacity Computations for Transmission, Distribution, and Industrial Applications , 1997 .

[9]  J. Ausen,et al.  Dynamic Thermal Rating System Relieves Transmission Constraint , 2006, ESMO 2006 - 2006 IEEE 11th International Conference on Transmission & Distribution Construction, Operation and Live-Line Maintenance.

[10]  Charles E. Roberts Systems of First-Order Differential Equations , 2010 .

[11]  T. Kusuda,et al.  EARTH TEMPERATURE AND THERMAL DIFFUSIVITY AT SELECTED STATIONS IN THE UNITED STATES , 1965 .