Indoor air quality audit implementation in a hotel building in Portugal

Abstract Hotels are designed to provide high levels of comfort for guests; however, frequent complaints related to uncomfortable thermal environment and inadequate indoor air quality (IAQ) appear. On the other hand, there is little research concerning IAQ audits of hotels up to now. This study is aimed to establish and demonstrate the comprehensive IAQ audit approach for hotel buildings, based on Portugal national laws. A 4-star hotel building in Portugal is used as a case study to demonstrate the IAQ audit application and evaluate its comprehensiveness and usefulness to the hotel or facility managers. The systematic approach involves the measurement of physical parameters – temperature (dry bulb), relative humidity and the concentration of the suspended particulate matter (PM10) – the monitoring of the concentrations of selected chemical indicators – carbon dioxide (CO2), carbon monoxide (CO), formaldehyde (HCHO) and total volatile organic compounds (TVOCs) – and the measurements of biological indicators (bacteria, fungi, Legionella). In the present case, air exchange rates are measured by the concentration-decay method using metabolic CO2 as the tracer gas. The comprehensive IAQ audit revealed four main problems in the hotel building: (1) insufficient ventilation rate; (2) too high particle concentration in some rooms; (3) contamination by Legionella of the sanitary hot-water circuit; (4) poor filtration effectiveness in all air handling units (AHUs).

[1]  K.W.D. Cheong,et al.  Development and application of an indoor air quality audit to an air-conditioned building in Singapore , 2001 .

[2]  David Coley,et al.  Carbon Dioxide Levels and Ventilation Rates in Schools , 2002 .

[3]  Reengineering in the Food-Service Industry Is It "Rightsizing?" , 1995 .

[4]  Che-Ming Chiang,et al.  Development and application of an integrated indoor air quality audit to an international hotel building in Taiwan , 2007, Environmental monitoring and assessment.

[5]  Y. Li,et al.  Role of air distribution in SARS transmission during the largest nosocomial outbreak in Hong Kong. , 2005, Indoor air.

[6]  Ivo Martinac,et al.  THERMAL COMFORT AND ENERGY SAVING IN THE HOTEL INDUSTRY , 2002 .

[7]  Wilco W. Chan,et al.  Indoor air quality in new hotels’ guest rooms of the major world factory region , 2009 .

[8]  P. Bohdanowicz,et al.  Determinants and benchmarking of resource consumption in hotels : Case study of Hilton international and Scandic in Europe , 2007 .

[9]  M. Niedrig,et al.  SARS: retrospective cohort study among German guests of the Hotel 'M', Hong Kong. , 2003, Euro surveillance : bulletin Europeen sur les maladies transmissibles = European communicable disease bulletin.

[10]  Roulet Claude-Alain,et al.  Simple and Cheap Air Change Rate Measurement Using CO2 Concentration Decays , 2002 .

[11]  Bjarne W. Olesen,et al.  The philosophy behind EN15251: Indoor environmental criteria for design and calculation of energy performance of buildings , 2007 .

[12]  S. Batterman,et al.  Indoor air quality in Michigan schools. , 2007, Indoor air.