배전계통에 사용되는 봉형 접지전극의 접지 특성 분석
暂无分享,去创建一个
Grounding system insures a reference potential point for electric devices and also provides a low impedance path for fault currents or transient currents in the earth. The ground impedance as function of frequency is necessary for determining its performance since fault currents could contain a wide range of frequencies. In this paper, the grounding resistance, grounding impedance and transient grounding impedance are measured by using 3-point fall-of-potential method in order to analyse grounding characteristics of the copper and concrete rod grounding electrodes. An equivalent transfer function model of the ground impedance and transient grounding impedance are identified from the measured values by using ARMA method and evaluated by comparing the conventional grounding impedance.