Simulation of CT's operating in parallel into a differential current protection scheme
暂无分享,去创建一个
When the secondaries of current transformers (CTs) are connected in parallel to a spill circuit with nonzero impedance, then the CT simulations are coupled by the common voltage across this spill circuit. This paper considers the case of two CTs feeding a high impedance spill circuit and gives a comparison of simulation and test results.
[1] P. G. McLaren,et al. Transformer core models based on the Jiles-Atherton algorithm , 1997, IEEE WESCANEX 97 Communications, Power and Computing. Conference Proceedings.
[2] D. Jiles,et al. Theory of ferromagnetic hysteresis , 1986 .
[3] W. W. L. Keerthipala,et al. Improved simulation models for current and voltage transformers in relay studies , 1992 .