Dynamic Thermal Modeling of MV/LV Prefabricated Substations

With the expansion and infilling of urban areas, the demand for electric power is driving the design and capacity of distribution substations to their thermal limits. Distribution transformer substations are increasingly required to be compact, reliable, safe, and intelligent. To efficiently utilize city space and to support the intermittent load flows imposed by smart-grid features, such as distributed generation, the transformers are expected to operate close to or occasionally over their ratings, with stalled or little air circulation inside the safety enclosure. Dynamic thermal models with physically validated convection and radiation heat-transfer components are essential for the real-time thermal rating of substations. Natural convection via the air inside the cabin to the outside ambient air plays the major role in cooling down a transformer. In this study a scale model of a prefabricated substation is examined to draft a numerical solution which is based on stack ventilation principles. A clear and expandable first principle approach is used to quantify heat transfer through ventilation openings. Measurements from actual cabins and 3-D finite element method simulations are used to validate the numerical model.

[1]  S. Maksimovic,et al.  Non-stationary thermal model of indoor transformer stations , 2002 .

[2]  Matti Lehtonen,et al.  Dynamic thermal modelling of power transformers , 2004 .

[3]  Tine Steen Larsen,et al.  Natural Ventilation Driven by Wind and Temperature Difference , 2006 .

[4]  A. Kalam,et al.  Performances of distribution transformers installed in metallic enclosures-an Australian experience , 2005, IEEE Transactions on Power Delivery.

[5]  A. Abdel-azim Fundamentals of Heat and Mass Transfer , 2011 .

[6]  N. Mortensen,et al.  Reexamination of Hagen-Poiseuille flow: shape dependence of the hydraulic resistance in microchannels. , 2004, Physical review. E, Statistical, nonlinear, and soft matter physics.

[7]  M. Lehtonen,et al.  Dynamic thermal modeling of power transformers: further Development-part I , 2006, IEEE Transactions on Power Delivery.

[8]  Ires Iskender,et al.  An improved nonlinear thermal model for MV/LV prefabricated oil-immersed power transformer substations , 2011 .

[9]  D J Swaffield,et al.  Rating methods for cables installed in unventilated and partially ventilated surface troughs , 2011, 2011 Electrical Insulation Conference (EIC)..

[10]  M. Lehtonen,et al.  Comparison of Air-Gap Thermal Models for MV Power Cables Inside Unfilled Conduit , 2012, IEEE Transactions on Power Delivery.

[11]  M. Stach,et al.  Assessment of overload capacity of power transformers by on-line monitoring systems , 2001, 2001 IEEE Power Engineering Society Winter Meeting. Conference Proceedings (Cat. No.01CH37194).