Study of HVDC Light for its enhancement of AC/DC interconnected transmission systems

This paper illustrates a study on HVDC light for its enhancement of AC/DC hybrid transmission system and multi-infeed HVDC system. In the sense of the realizing independent controlling of active and reactive power, HVDC light is more effective compared to the conventional HVDC system. An AC/DC parallel transmission system and a three-infeed HVDC system are modeled using PSCAD/EMTDC. Simulations corresponding to different situations are performed. From the simulation results, HVDC light is proven to be able to improve the rotor angle stability and dynamic performance of AC/DC interconnected transmission system, and support the AC voltage during the system fault to enlarge the margin of the voltage stability which is the basic difference from conventional HVDC. HVDC light can also prevent commutation failure in multi-infeed HVDC system and help the recovery of HVDC system too.

[1]  Yao Zhang,et al.  Studies of Commutation Failures in HVDC System Based on Hypersim , 2006, 2006 International Conference on Power System Technology.

[2]  Lie Xu,et al.  Topologies for VSC transmission , 2001 .

[3]  D. N. Kosterev Modeling synchronous voltage source converters in transmission system planning studies , 1997 .

[4]  B.T. Ooi,et al.  VSC-HVDC station with SSSC characteristics , 2003, IEEE 34th Annual Conference on Power Electronics Specialist, 2003. PESC '03..

[5]  Byung-Moon Han,et al.  Back-to-back HVDC system using a 36-step voltage source converter , 2006 .

[6]  Liangzhong Yao,et al.  Grid Integration of Large DFIG-Based Wind Farms Using VSC Transmission , 2007, IEEE Transactions on Power Systems.

[7]  M. Szechtman,et al.  A benchmark model for HVDC system studies , 1991 .

[8]  Yao Zhang,et al.  Constructive nonlinear control of the parallel AC/DC transmission system , 2006, 2006 IEEE Power Engineering Society General Meeting.

[9]  Zhang Yao,et al.  Coordinated control of interarea oscillation in the China Southern power grid , 2006 .

[10]  M. R. Iravani,et al.  Application of GTO voltage source inverter in a hybrid HVDC link , 1994 .

[11]  P. Kundur,et al.  Power system stability and control , 1994 .

[12]  Chang Hsin Chien,et al.  Analysis of Harmonics in Subsea Power Transmission Cables Used in VSC–HVDC Transmission Systems Operating Under Steady-State Conditions , 2007, IEEE Transactions on Power Delivery.

[13]  W.L. Kling,et al.  HVDC Connection of Offshore Wind Farms to the Transmission System , 2007, IEEE Transactions on Energy Conversion.

[14]  Boon-Teck Ooi,et al.  Exploiting voltage support of voltage-source HVDC , 2003 .

[15]  M. Szechtman,et al.  First benchmark model for HVDC control studies , 1991 .