A simple instant‐estimation method for time‐average quantities of single‐phase power and application to single‐phase power grid connection by inverter
暂无分享,去创建一个
This paper presents and analyzes a new simple instant-estimation method for time-average quantities such as rms values of voltage and current, active and reactive powers, and power factor for single-phase power with the fundamental component of constant or nearly constant frequency by measuring instantaneous values of voltage and current. According to the analyses, the method can instantly estimate time-average values with accuracy of the fundamental frequency, and estimation accuracy of the power factor is about two times better than that of voltage, current, and powers. The instant-estimation method is simple and can be easily applied to single-phase power control systems that are expected to control instantly and continuously power factor on a single-phase grid by inverter. Based on the proposed instant-estimation method, two methods for such power control systems are also proposed and their usefulness is verified through simulations. © 2007 Wiley Periodicals, Inc. Electr Eng Jpn, 159(2): 34–43, 2007; Published online in Wiley InterScience (www.interscience.wiley.com). DOI 10.1002/eej.20236
[1] T. Shimizu,et al. Generalized theory of instantaneous active and reactive powers in single-phase circuits based on Hilbert transform , 2002, 2002 IEEE 33rd Annual IEEE Power Electronics Specialists Conference. Proceedings (Cat. No.02CH37289).