Controlled Closing of PT Delta Winding for Identifying Faulted Lines

It is very difficult to identify the line experiencing a single-phase to ground fault in ungrounded and resonant grounded systems. This paper presents a scheme for faulted line identification based on the concept of converting the ungrounded system into a grounded system in a controlled manner. This conversion or controlled grounding is done through the delta-winding of the potential transformers commonly available in substations. The delta-winding is inserted with a pair of SCRs and the controlled conduction of the SCRs results in a temporarily closed delta and thus creating a temporarily grounded system. This scheme is very easy to implement and does not involve high voltage components. Results of theoretical analysis, computer simulation and lab experiments have confirmed the effectiveness of the proposed method.

[1]  Zeng Xiang,et al.  NEW METHODS FOR CONTROL AND PROTECTION RELAY IN A COMPENSATED MEDIUM VOLTAGE DISTRIBUTION NETWORK BASED ON INJECTING VARIOUS FREQUENCY CURRENT , 2000 .

[2]  D. Lubkeman,et al.  Fault locating in ungrounded and high-resistance grounded systems , 2000, Record of Conference Papers. Industry Applications Society Forty-Seventh Annual Conference. 2000 Petroleum and Chemical Industry Technical Conference (Cat. No.00CH37112).

[3]  D. H. Lubich High resistance grounding and fault finding on three phase three wire (delta) power systems , 1997, 1997 IEEE Annual Textile, Fiber and Film Industry Technical Conference.

[4]  T. Baldwin,et al.  Fault locating in ungrounded and high-resistance grounded systems , 2001, 2001 IEEE Industrial and Commercial Power Systems Technical Conference. Conference Record (Cat. No.01CH37226).

[5]  J.P. Nelson,et al.  High resistance grounding of low voltage systems: a standard for the petroleum and chemical industry , 1996, Proceedings of 1996 IAS Petroleum and Chemical Industry Technical Conference.

[6]  J. C. Das,et al.  Grounding of AC and DC low-voltage and medium-voltage drive systems , 1998 .

[7]  Peng Zhang,et al.  Identification of the Faulted Distribution Line Using Thyristor-Controlled Grounding , 2009, IEEE Transactions on Power Delivery.

[8]  Zhang Jie Analysis and improvement of the 'S injection' fault feeder detection method , 2007 .

[9]  F. Renovich,et al.  Directional ground-fault indicator for high-resistance grounded systems , 2003 .