Efficient ground grid designs in layered soils

A detailed analysis of the effects of ground grid configuration on grounding performance has been carried out for uniform and horizontally stratified soils with multiple layers. The results of the analysis reveal that the most efficient and cost-effective design is highly dependent on soil structure type and characteristics. In the absence of ground rods, grounding grids with uniform mesh size are quite efficient in soils having a thin (relative to grid size) high resistivity (relative to the lower layers) top soil, while grids with small mesh size at the periphery of the grid provide optimum performance in uniform soils and soils with low resistivity top soils. Ground rods were found to be effective only when a significant portion of their length is in contact with a low resistivity soil, as expected.