Review on protection coordination strategies and development of an effective protection coordination system for DC microgrid

In this paper, common DC-fault detection methods have been reviewed. Effects of two line-to-line and line-to-ground fault types from various fault locations to operation of the DC system are presented. In addition, operation principle, strong and weak points of four main types of protection devices (including fuses, no-fuse circuit breakers, power-electronic protection devices and protective relays) are mentioned. Each different type of protection devices has the ability to protect and isolate different components of the DC microgrid (e.g. power converter, PV system, battery system, capacitor and others) under fault occurrences. The paper analyses possible protection coordination strategies of protection devices to ensure safety of any components in the DC microgrid. These summarized coordination strategies can be suitable for any DC microgrid configurations. In the next content, an effective protection coordination system of a real community-sized DC microgrid is developed, which use fast-acting fuses to replace no-fuse circuit breakers already installed at some certain locations in the DC microgrid. Aims of this improved protection coordination system are to shorten critical fault clearing time and get the cost effectiveness while still ensuring high selectivity, dependability and safety of the DC microgrid. As a result, the no-fuse circuit breakers placed at locations such as: output of PV arrays, output of the battery, output of the fuel-cell system, and terminals of power converters are efficiently replaced by the fast-acting fuses. Additionally, protection devices located at load feeders are suggested to use the relays to optimise the coordination time between main and back-up protection in case of faults occurring at the load feeders.

[1]  A.R. Bendre,et al.  IGCTs vs. IGBTs for circuit breakers in advanced ship electrical systems , 2009, 2009 IEEE Electric Ship Technologies Symposium.

[2]  Jae-Do Park,et al.  Fault Detection and Isolation in Low-Voltage DC-Bus Microgrid System , 2013, IEEE Transactions on Power Delivery.

[3]  Boon-Teck Ooi,et al.  Protection of VSC-multi-terminal HVDC against DC faults , 2002, 2002 IEEE 33rd Annual IEEE Power Electronics Specialists Conference. Proceedings (Cat. No.02CH37289).

[4]  Chul-Hwan Kim,et al.  A study on the fault characteristics of line fault in LVDC distribution system , 2014 .

[5]  J.-M. Meyer,et al.  A DC hybrid circuit breaker with ultra-fast contact opening and integrated gate-commutated thyristors (IGCTs) , 2006, IEEE Transactions on Power Delivery.

[6]  Jing Yong,et al.  Investigation on the system grounding types for low voltage direct current systems , 2013, 2013 IEEE Electrical Power & Energy Conference.

[7]  Ju Lee,et al.  AC-microgrids versus DC-microgrids with distributed energy resources: A review , 2013 .

[8]  A. Sannino,et al.  Protection of Low-Voltage DC Microgrids , 2009, IEEE Transactions on Power Delivery.

[9]  Akira Kawakami,et al.  High-power semiconductor device: a symmetric gate commutated turn-off thyristor , 2001 .

[10]  O. Nakamura,et al.  400 V class high-speed current limiting circuit breaker for electric power system , 1994 .

[11]  R.H. Lasseter,et al.  Microgrid: a conceptual solution , 2004, 2004 IEEE 35th Annual Power Electronics Specialists Conference (IEEE Cat. No.04CH37551).

[12]  Alex Q. Huang,et al.  The emitter turn-off thyristor-based DC circuit breaker , 2002, 2002 IEEE Power Engineering Society Winter Meeting. Conference Proceedings (Cat. No.02CH37309).

[13]  Jörgen Svensson,et al.  Fault Detection and Clearance in DC Distributed Power Systems , 2002 .

[14]  Min Luo,et al.  Wavelet based method for fault detection in Medium Voltage DC shipboard power systems , 2012, 2012 IEEE International Instrumentation and Measurement Technology Conference Proceedings.

[15]  Naveen Kumar Chanda,et al.  ANN-based fault classification and location in MVDC shipboard power systems , 2011, 2011 North American Power Symposium.

[16]  M.E. Baran,et al.  Overcurrent Protection on Voltage-Source-Converter-Based Multiterminal DC Distribution Systems , 2007, IEEE Transactions on Power Delivery.

[17]  P. Steimer,et al.  IGCT technology baseline and future opportunities , 2001, 2001 IEEE/PES Transmission and Distribution Conference and Exposition. Developing New Perspectives (Cat. No.01CH37294).

[18]  C. S. Chang,et al.  Real-time detection using wavelet transform and neural network of short-circuit faults within a train in DC transit systems , 2001 .

[19]  Ambra Sannino,et al.  Centralized ac/dc Power Conversion for Electronic Loads in a Low-Voltage dc Power System , 2006 .