Flow meter fault isolation in building central chilling systems using wavelet analysis

Abstract This paper presents an approach to isolate flow meter faults in building central chilling systems. It mathematically explains the fault collinearity among the flow meters in central chilling systems and points out that the sensor validation index (SVI) used in principal component analysis (PCA) is incapable of isolating flow meter faults due to the fault collinearity. The wavelet transform is used to isolate the flow meter faults as a substitute for the SVI of PCA. This approach can identify various variations in measuring signals, such as ramp, step, discontinuity etc., due to the good property of the wavelet in local time–frequency. Some examples are given to demonstrate its ability of fault isolation for the flow meters.

[1]  Ronald N. Bracewell,et al.  The Fourier Transform and Its Applications , 1966 .

[2]  David Salesin,et al.  Wavelets for computer graphics - theory and applications , 1996, The Morgan Kaufmann series in computer graphics and geometric modeling.

[3]  Thomas F. Edgar,et al.  Identification of faulty sensors using principal component analysis , 1996 .

[4]  Dennis Gabor,et al.  Theory of communication , 1946 .

[5]  Manus P. Henry,et al.  The self-validating sensor: rationale, definitions and examples , 1993 .

[6]  John F. MacGregor,et al.  Multivariate SPC charts for monitoring batch processes , 1995 .

[7]  Shahriar Negahdaripour,et al.  An Innovation-Based Methodology for HVAC System Fault Detection , 1985 .

[8]  G. Strang Wavelet transforms versus Fourier transforms , 1993, math/9304214.

[9]  Shengwei Wang,et al.  Robust sensor fault diagnosis and validation in HVAC systems , 2002 .

[10]  Dominique Bonvin,et al.  Factor Analytical Modeling of Biochemical Data , 1995 .

[11]  Ron J. Patton,et al.  Robust Model-Based Fault Diagnosis: The State of the ART , 1994 .

[12]  Moncef Krarti,et al.  Review of laboratory and field methods to measure fan, pump, and chiller performance , 1997 .

[13]  Shengwei Wang,et al.  Dynamic simulation of a building central chilling system and evaluation of EMCS on-line control strategies , 1998 .

[14]  S. Joe Qin,et al.  Joint diagnosis of process and sensor faults using principal component analysis , 1998 .

[15]  Shengwei Wang,et al.  Law-based sensor fault diagnosis and validation for building air-conditioning systems , 1999 .

[16]  Youming Chen,et al.  Sensor validation and reconstruction for building central chilling systems based on principal component analysis , 2004 .