The Comparison Study of Harmonic Detection Algorithms for Single-Phase Power Systems

This paper presents a comparison study of harmonic detection algorithms for single-phase power systems. The three harmonic detection algorithms are compared, instantaneous reactive power (PQ), synchronous reference frame (SRF) and sliding window with Fourier analysis (SWFA). These algorithms are used to calculate the reference current of a shunt active power filter. For testing the algorithms performance, MATLAB/Simulink is used to simulate the harmonic elimination system with two cases of voltage source, the pure sinusoidal voltage source and the distorted voltage source. The factors to indicate the harmonic detection performance are the total harmonic distortion percentage of current (%THDi) and power factor (PF) values of source current after compensation. The simulation results show that the SWFA provides the best %THDi compared with the PQ and SRF algorithms in both two cases voltage source. Furthermore, the PQ and SRF algorithms can improve the power factor of electric system.

[1]  Kongpan Areerak,et al.  A New Design Approach of Fuzzy Controller for Shunt Active Power Filter , 2015 .

[2]  M. El-Habrouk,et al.  Design and implementation of a modified Fourier analysis harmonic current computation technique for power active filters using DSPs , 2001 .

[3]  Proportional–integral/proportional–integral-derivative tuning procedure of a single-phase shunt active power filter using Bode diagram , 2014 .

[4]  A. Hiranandani Calculation of cable ampacities including the effects of harmonics , 1998 .

[5]  Jinjun Liu,et al.  A new approach for single-phase harmonic current detecting and its application in a hybrid active power filter , 1999, IECON'99. Conference Proceedings. 25th Annual Conference of the IEEE Industrial Electronics Society (Cat. No.99CH37029).

[6]  Hirofumi Akagi,et al.  Instantaneous Reactive Power Compensators Comprising Switching Devices without Energy Storage Components , 1984, IEEE Transactions on Industry Applications.

[7]  F. Pazos,et al.  DQ transformation development for single-phase systems to compensate harmonic distortion and reactive power , 2004, 9th IEEE International Power Electronics Congress, 2004. CIEP 2004.

[8]  Pekik Argo Dahono,et al.  New hysteresis current controller for single-phase full-bridge inverters , 2009 .

[9]  Chi-Seng Lam,et al.  Comparison among PPF, APF, HAPF and a combined system of a shunt HAPF and a shunt thyristor controlled LC , 2015, TENCON 2015 - 2015 IEEE Region 10 Conference.

[10]  R. D. Henderson,et al.  Harmonics: the effects on power quality and transformers , 1994, [Proceedings] IEEE 1993 Annual Textile, Fiber and Film Industry Technical Conference.

[11]  Chang-Ming Liaw,et al.  A robust hysteresis current-controlled PWM inverter for linear PMSM driven magnetic suspended positioning system , 2001, IEEE Trans. Ind. Electron..