Implementation and evaluation of a labscale synchrophasor model and applications
暂无分享,去创建一个
This paper presents a preliminary implementation of a Labscale Synchrophasor model, where one SEL-2402 (Satellite Synchronized Clock) and SEL-451 relay is installed and properly configured. The synchrophasor data is metered in realtime and displayed graphically. For the purpose of analysis and developing the backend applications, the Phasor Measurement Unit (PMU) data is archived using openPDC. An important backend power system application is then implemented which utilizes the archived synchrophasor data. The application implements an algorithm to screen the moving window of PMU data for event detection. The algorithm uses three different methods to screen for possible events viz., Min-Max method, Fast Fourier Transform method and Pencil-Matrix method. Each method is applied to a moving window of PMU data. The event detection algorithm is tested on the PMU data obtained from the Real Time Digital Simulator (RTDS).
[1] A.G. Phadke,et al. Wide Area Protection and Control - Today and Tomorrow , 2006, 2005/2006 IEEE/PES Transmission and Distribution Conference and Exhibition.
[2] Surya Santoso,et al. Algorithm for Screening Phasor Measurement Unit Data for Power System Events and Categories and Common Characteristics for Events Seen in Phasor Measurement Unit Relative Phase-Angle Differences and Frequency Signals , 2013 .