A wavelet multiresolution-based analysis for location of the point of strike of a lightning overvoltage on a transmission line

Lightning flashes on extremely high voltage lines are quite common and can lead to insulation breakdown or other line hardware failure causing disruption in supply. An accurate location of the site of failure will result in faster maintenance and restoration of supply. In this paper, a novel technique based on the wavelet multiresolution analysis (MRA) for locating the point of strike of a lightning overvoltage on a transmission line is presented. Lightning strikes at different points on a 400-kV transmission line of different line lengths are simulated by shifting the point of strike of the lightning impulse every 5 km. The Electromagnetic Transient Program (EMTP) [Microtran] is employed to generate the time-domain input signal. Daubechies eight (D8) Wavelet transform is used to analyze lightning overvoltages. The tenth level output of MRA detail signals extracted from the original signals is used as the criterion for the analysis. Extensive simulation work has been done and results indicate that the proposed scheme is very effective in locating the point of strike with reasonable accuracy.

[1]  A. M. Mousa,et al.  GPS travelling wave fault locator systems: investigation into the anomalous measurements related to lightning strikes , 1996 .

[2]  Ingrid Daubechies,et al.  The wavelet transform, time-frequency localization and signal analysis , 1990, IEEE Trans. Inf. Theory.

[3]  Paulo F. Ribeiro,et al.  Exploring the power of wavelet analysis , 1996 .

[4]  I. Daubechies Orthonormal bases of compactly supported wavelets , 1988 .

[5]  Chen Xiangxun,et al.  Travelling wave fault location of transmission line using wavelet transform , 1998, POWERCON '98. 1998 International Conference on Power System Technology. Proceedings (Cat. No.98EX151).

[6]  P. G. McLaren,et al.  Distance Protection Based on Traveling Waves , 1983, IEEE Power Engineering Review.

[7]  Amara Lynn Graps,et al.  An introduction to wavelets , 1995 .

[8]  J. S. Mayer,et al.  Wavelets and electromagnetic power system transients , 1996 .

[9]  Ali Abur,et al.  Use of time delays between modal components in wavelet based fault location , 2000 .

[10]  Jie Liang,et al.  Application of wavelet transform in travelling wave protection , 2000 .

[11]  Witold Kinsner,et al.  Wavelet modelling of transients in power systems , 1997, IEEE WESCANEX 97 Communications, Power and Computing. Conference Proceedings.

[12]  P. Crossley,et al.  Distance Protection Based on Travelling Waves , 1983, IEEE Transactions on Power Apparatus and Systems.

[13]  Y. H. Song,et al.  Wavelet analysis based scheme for fault detection and classification in underground power cable systems , 2000 .

[14]  A. Greenwood,et al.  Electrical transients in power systems , 1971 .

[15]  Stéphane Mallat,et al.  A Theory for Multiresolution Signal Decomposition: The Wavelet Representation , 1989, IEEE Trans. Pattern Anal. Mach. Intell..

[16]  F. Asamoah Discrete Wavelet Analysis of Signals , 1999 .