INFLUENCE OF DESIGN AND OPERATING CONDITIONS ON THE SYSTEM PERFORMANCE OF A TWO-STAGE ADSORPTION CHILLER

This article aims at clarifying the possible design and operating conditions for silica gel-water adsorption refrigeration cycles driven by near-ambient temperature waste heat sources (between 45 and 75°C) with relatively small regenerating temperature lifts (15 to 45 K). A two-stage silica gel-water advanced adsorption chiller is introduced and a simulation model of the chiller was developed to analyze the influence of operating and design conditions on the system performance (coefficient of performance, COP, and cooling capacity). It was hypothesized that the proposed chiller can be driven by low temperature waste heat at 55°C to produce effective cooling. Simulation results show that the operating conditions such as cycle time and hot and cooling water inlet temperature have an influential effect on cooling capacity and COP. COP is proportional to cycle time and heat transfer coefficient as well as inversely proportional to the cooling water inlet temperature, while there are optimum values of hot water temperature and silica gel weight for maximum COP. Cooling capacity mainly improves with the addition of silica gel weight and decreases as cooling water temperature increases. Simulation results also revealed that the system performance can be improved significantly by setting the design and operating conditions optimally.

[1]  Takao Kashiwagi,et al.  Modeling the performance of two-bed, sillica gel-water adsorption chillers , 1999 .

[2]  Alam K C Amanul Design Aspects of Adsorption Refrigeration Systems , 2001 .

[3]  Motoyuki Suzuki,et al.  AIR DRYING BY PRESSURE SWING ADSORPTION , 1983 .

[4]  Takao Kashiwagi,et al.  Computational analysis of an advanced adsorption-refrigeration cycle , 1995 .

[5]  Ling Wang,et al.  Performance estimation of an adsorption cooling system for automobile waste heat recovery , 1997 .

[6]  Akiyoshi Sakoda,et al.  FUNDAMENTAL STUDY ON SOLAR POWERED ADSORPTION COOLING SYSTEM , 1984 .

[7]  F. Meunier Theoretical performances of solid adsorbent cascading cycles using the zeolite-water and active carbon-methanol pairs: four case studies , 1986 .

[8]  Francis Meunier,et al.  Experimental study of cascading adsorption cycles , 1989 .

[9]  J. J. Guilleminot,et al.  Design of an experimental solar-powered, solid-adsorption ice maker , 1986 .

[10]  Takao Kashiwagi,et al.  Entropy generation analysis of two-bed, silica gel-water, non-regenerative adsorption chillers , 1998 .

[11]  William J. Wepfer,et al.  Square wave analysis of the solid-vapor adsorption heat pump , 1989 .

[12]  Robert E. Critoph,et al.  Forced convection adsorption cycles , 1998 .

[13]  William J. Wepfer,et al.  Ramp Wave Analysis of the Solid/Vapor Heat Pump , 1990 .

[14]  Takao Kashiwagi,et al.  Multi-bed regenerative adsorption chiller - improving the utilization of waste heat and reducing the chilled water outlet temperature fluctuation , 2001 .

[15]  Yong Tae Kang,et al.  Heat exchanger design effect on the system performance of silica gel adsorption refrigeration systems , 2000 .