Methodology for grid voltage unbalance compensation appling a two-converter series DFIG topology

This paper presents a new control strategy for the DFIG replacing the conventional Grid Side Converter for a series one, namely series grid side converter (SGSC). The control strategy for operation under grid voltage unbalance intends not only the ideal machine operation, but also to attenuate the grid voltage unbalance. This compensation is performed injecting unbalanced currents in the point of common coupling (PCC). The SGSC promotes a higher operational capacity during grid disturbances as voltage unbalances. The proposed methodology uses the machine electromagnetic power equation decomposed by the symmetrical components to obtain a relationship between the rotor negative sequence current and the stator negative sequence voltage, where the oscillating components of the electromagnetic power are zero. Appling this relationship is possible to reduce the electromagnetic torque oscillations when injecting negative sequence current by the machine stator.

[1]  N. Mohan,et al.  Control of a Doubly Fed Induction Wind Generator Under Unbalanced Grid Voltage Conditions , 2007, IEEE Transactions on Energy Conversion.

[2]  N. Mohan,et al.  New Scheme to Connect DFIG to Power Grid , 2006, IECON 2006 - 32nd Annual Conference on IEEE Industrial Electronics.

[3]  Barry W. Williams,et al.  Compensation of network voltage unbalance using doubly fed induction generator-based wind farms , 2009 .

[4]  Alexander E. Emanuel,et al.  A novel control system for harmonic compensation by using Wind Energy Conversion based on DFIG technology , 2010, 2010 Twenty-Fifth Annual IEEE Applied Power Electronics Conference and Exposition (APEC).

[5]  Lie Xu,et al.  Dynamic Modeling and Control of DFIG-Based Wind Turbines Under Unbalanced Network Conditions , 2007, IEEE Transactions on Power Systems.

[6]  Jiabing Hu,et al.  Coordinated Control of DFIG's RSC and GSC Under Generalized Unbalanced and Distorted Grid Voltage Conditions , 2013, IEEE Transactions on Industrial Electronics.

[7]  Kai Zhuang,et al.  Operation and control of a grid-connected DFIG-based wind turbine with series grid-side converter during network unbalance , 2011 .

[8]  H. Pinheiro,et al.  Design and control of doubly-fed induction generators with series grid-side converter , 2008, 2008 34th Annual Conference of IEEE Industrial Electronics.

[9]  G. Venkataramanan,et al.  A Fault Tolerant Doubly Fed Induction Generator Wind Turbine Using a Parallel Grid Side Rectifier and Series Grid Side Converter , 2008, IEEE Transactions on Power Electronics.

[10]  Kankar Bhattacharya,et al.  Stability Analysis of Unbalanced Distribution Systems With Synchronous Machine and DFIG Based Distributed Generators , 2014, IEEE Transactions on Smart Grid.

[11]  A. Chandra,et al.  Grid-side converter control of DFIG wind turbines to enhance power quality of distribution network , 2006, 2006 IEEE Power Engineering Society General Meeting.

[12]  Jiabing Hu,et al.  Integrated Modeling and Enhanced Control of DFIG Under Unbalanced and Distorted Grid Voltage Conditions , 2012, IEEE Transactions on Energy Conversion.

[13]  I. Erlich,et al.  Performance Evaluation of New Series Connected Grid-Side Converter of Doubly-Fed Induction Generator , 2008, 2008 Joint International Conference on Power System Technology and IEEE Power India Conference.

[14]  Vincente Ciancio,et al.  The New Grid , 2016 .

[15]  Turan Gonen Modern power system analysis , 1988 .