Influence of grading capacitor of multiple‐break circuit breaker on the extinction of secondary arc – a new method for reducing dead time

To guarantee the uniform distribution of transient recovery voltage for double-break circuit breaker, grading capacitors are often installed in parallel with each interrupter unit. In this study, the influence of the capacitors on the secondary arc is systematically investigated. First, the equivalent circuit for ultra high voltage transmission line is developed. Taking the capacitor into account, the formulas for the arc current and the recovery voltage, not only the steady state but also the transient, are derived. Meanwhile, the dynamic models for primary arc and secondary arc models have been established in the environment of EMTP. Then, a series of simulations have been performed. The impact of the capacitor on the key quantities of secondary arc, such as the rate of rise of recovery voltage, the arcing time, and the maximum instantaneous current, is comparatively analysed. Furthermore, the capacitor can be extended to suppress the secondary arc, and a novel method is proposed in this study. The operating principle of this method is presented, and its effectiveness is validated through electromagnetic transient simulations. For practical implementation, the technical requirement is finally discussed. The proposed method is simple in structure, and it provides an alternative to the neutral reactor.

[1]  A. T. Johns,et al.  An Alternative Approach to Adaptive Single-Pole Auto Reclosing in High-Voltage Transmission Systems Based on Variable Dead Time Control , 2001, IEEE Power Engineering Review.

[2]  Eugeniusz Rosolowski,et al.  Arc effect on single-phase reclosing time of a UHV power transmission line , 2004 .

[3]  A. C. Legate,et al.  The Application of High-Speed Grounding Switches for Single-Pole Reclosing on 500 kV Power Systems , 1981 .

[4]  D. Koenig,et al.  Influence of grading capacitors on the breaking performance of a 24-kV vacuum breaker series design , 2003 .

[5]  Xu Zhang,et al.  Compensating scheme for limiting secondary arc current of 1000 kV ultra-high voltage long parallel lines , 2013 .

[6]  L. van der Sluis,et al.  A new synthetic test circuit for ultra-high-voltage circuit breakers , 1997 .

[7]  Zhang Kun Review of Grading Capacitors of Multi-break Vacuum Circuit Breakers , 2011 .

[8]  A. T. Johns,et al.  Improved techniques for modelling fault arcs an faulted EHV transmission systems , 1994 .

[9]  G. Ban,et al.  Testing EHV secondary arcs , 2001, 2001 IEEE Porto Power Tech Proceedings (Cat. No.01EX502).

[10]  M.R.D. Zadeh,et al.  Investigation of Neutral Reactor Performance in Reducing Secondary Arc Current , 2008, IEEE Transactions on Power Delivery.

[11]  E. W. Kimbark,et al.  Suppression of Ground-Fault Arcs on Single-Pole-Switched EHV Lines by Shunt Reactors , 1964 .

[12]  A. P. Strom Long 60-Cycle Arcs in Air , 1946, Transactions of the American Institute of Electrical Engineers.

[13]  P. R. Drum,et al.  Protective relaying performance reporting , 1992 .

[14]  C. Shih,et al.  Single Phase Switching Tests on the AEP 765 KV System-Extinction Time for Large Secondary Arc Currents , 1983, IEEE Transactions on Power Apparatus and Systems.

[15]  A.A. Girgis,et al.  Fault location on a transmission line using synchronized Voltage measurements , 2004, IEEE Transactions on Power Delivery.

[16]  M. A. Redfern,et al.  Characterization of ferroresonant modes in HV substation with CB grading capacitors , 2007 .

[17]  J. Talaisys,et al.  Voltage harmonic content of long artificially generated electrical arc in out-door experiment at 500 kV towers , 2014, IEEE Transactions on Dielectrics and Electrical Insulation.

[18]  Xu Zhang,et al.  Optimal compensating scheme for limiting secondary arc current of 1000-kV UHV short parallel lines , 2012 .

[19]  Li Zhi-bing Simulation for Secondary Arc Caused by Single-phase Grounding in UHV AC Transmission Line , 2010 .

[20]  B. J. Ware,et al.  Compensation Scheme for Single-Pole Switching on Untransposed Transmission Lines , 1978, IEEE Transactions on Power Apparatus and Systems.

[21]  H. N. Scherer,et al.  Single Phase Switching Tests on 765 kV and 750 kV Transmission Lines , 1985, IEEE Power Engineering Review.

[22]  Yi Hu,et al.  Ultra High Voltage Transmission in China: Developments, Current Status and Future Prospects , 2009, Proceedings of the IEEE.