Analysis of electromagnetic forces in high voltage superconducting fault current limiters with saturated core

This paper presents a three-dimensional numerical analysis of the electromagnetic forces within a high voltage superconducting Fault Current Limiter (FCL) with a saturated core under short-circuit conditions. The effects of electrodynamics forces in power transformer coils under short-circuit conditions have been reported widely. However, the coil arrangement in an FCL with saturated core differs significantly from existing reactive devices. The boundary element method is employed to perform an electromagnetic force analysis on an FCL. The analysis focuses on axial and radial forces of the AC coil. The results are compared to those of a power transformer and important design considerations are highlighted.

[1]  M. R. Patel Dynamic stability of helical and barrel coils in transformers against axial short - circuit forces , 1980 .

[2]  W. J. McNutt,et al.  Power Transformen Short-Circuit Strength - Requirements, Design, and Demonstration , 1970 .

[3]  S.V. Kulkarni,et al.  Analysis of Short Circuit Performance of Split-Winding Transformer Using Coupled Field-Circuit Approach , 2007, 2007 IEEE Power Engineering Society General Meeting.

[4]  W. B. Hall,et al.  Application of rotating arc SF6 interrupter design to the highest distribution voltage levels , 1998 .

[5]  Jianguo Zhu,et al.  Transient Simulation and Analysis for Saturated Core High Temperature Superconducting Fault Current Limiter , 2006 .

[6]  Antonio Morandi,et al.  State of the art of superconducting fault current limiters and their application to the electric power system , 2013 .

[7]  A. C. Delaiba,et al.  Transformer mechanical stress caused by external short-circuit: a time domain approach , 2007 .

[8]  Shigeru Shida,et al.  Mechanical Strength of Transformer Windings under Short-Circuit Conditions , 1969 .

[9]  W.J. McNutt,et al.  Transformer short-circuit strength and standardsߞA state-of-the-art paper , 1975, IEEE Transactions on Power Apparatus and Systems.

[10]  P. J. Costa Branco,et al.  Proposal for an RMS thermoelectric model for a resistive-type superconducting fault current limiter (SFCL) , 2010 .

[11]  J. Faiz,et al.  Three- and Two-Dimensional Finite-Element Computation of Inrush Current and Short-Circuit Electromagnetic Forces on Windings of a Three-Phase Core-Type Power Transformer , 2008, IEEE Transactions on Magnetics.

[12]  Frank Darmann,et al.  Design and development of a 3-Phase saturated core High Temperature Superconducting Fault Current Limiter , 2009, 2009 International Conference on Electric Power and Energy Conversion Systems, (EPECS).

[13]  Yong-Sun Cho,et al.  The operation stability of a three-phase matrix-type SFCL against break-down of superconducting elements , 2010 .

[14]  F. Moriconi,et al.  Development and Deployment of Saturated-Core Fault Current Limiters in Distribution and Transmission Substations , 2011, IEEE Transactions on Applied Superconductivity.

[15]  E. T. Norris Mechanical strength of power transformers in service , 1957 .

[16]  Franco Moriconi,et al.  An innovative compact saturable-core HTS Fault Current Limiter - development, testing and application to transmission class networks , 2010, IEEE PES General Meeting.

[17]  M. Waters,et al.  The short-circuit strength of power transformers , 1966 .