Analysis of Power Flow in UPQC during Voltage Sag and Swell Conditions for Selection of Device Ratings

This paper deals with the steady state analysis of unified power quality conditioner (UPQC). The UPQC, a combination of shunt and series active power filter (APF), is one of the best solutions towards the mitigation of voltage sags and swells problems on distribution network. The mathematical analysis is based on active and reactive power flow through the shunt and series APF, wherein series APF can absorb or deliver the active power whereas the reactive power requirement is totally handled by shunt APF alone during all conditions. The derived relationship between source current and % of sag/swell variation shows shunt APF plays an important role in maintaining the overall power balance in the entire network. The digital simulation is carried out to verify the analysis done. The simulation results support the mathematical analysis. The effect of load VAR variation and the impact of % sag/swell on the kVA ratings of both shunt and series APF are also analyzed. This analysis can be very useful for selection of device ratings for both shunt and series APFs

[1]  A. Elnady,et al.  New functionalities of the unified power quality conditioner , 2001, 2001 IEEE/PES Transmission and Distribution Conference and Exposition. Developing New Perspectives (Cat. No.01CH37294).

[2]  A. T. Johns,et al.  Control concept of Unified Power Line Conditioner , 2000, 2000 IEEE Power Engineering Society Winter Meeting. Conference Proceedings (Cat. No.00CH37077).

[3]  A. Elnady,et al.  New functionalities of an adaptive unified power quality conditioner , 2001, 2001 Power Engineering Society Summer Meeting. Conference Proceedings (Cat. No.01CH37262).

[4]  S. Muthu,et al.  Steady-state operating characteristics of unified active power filters , 1997, Proceedings of APEC 97 - Applied Power Electronics Conference.

[5]  A. Ghosh,et al.  A unified power quality conditioner for voltage regulation of critical load bus , 2004, IEEE Power Engineering Society General Meeting, 2004..

[6]  Kamal Al-Haddad,et al.  A review of active filters for power quality improvement , 1999, IEEE Trans. Ind. Electron..

[7]  M. T. Tsai Analysis and design of a cost-effective series connected AC voltage regulator , 2004 .

[8]  A. Chandra,et al.  A simple new control technique for unified power quality conditioner (UPQC) , 2004, 2004 11th International Conference on Harmonics and Quality of Power (IEEE Cat. No.04EX951).

[9]  Malabika Basu,et al.  Performance study of UPQC-Q for load compensation and voltage sag mitigation , 2002, IEEE 2002 28th Annual Conference of the Industrial Electronics Society. IECON 02.

[10]  Kamal Al-Haddad,et al.  An improved control algorithm of shunt active filter for voltage regulation, harmonic elimination, power-factor correction, and balancing of nonlinear loads , 2000 .

[11]  Hirofumi Akagi,et al.  New trends in active filters for improving power quality , 1996, Proceedings of International Conference on Power Electronics, Drives and Energy Systems for Industrial Growth.