Control topology options for single-phase UPS inverters

Several control topologies for single-phase UPS inverters are presented and compared, with the common objective of providing a dynamically stiff, low THD, sinusoidal output voltage. Full state feedback, full state command controllers are shown utilizing both filter inductor current and filter capacitor current feedback to augment output voltage control. All controllers presented include output voltage decoupling in a manner analogous to "back-EMF" decoupling in DC motor drives. Disturbance input decoupling of the load current and its derivative is presented. An observer-based controller is additionally considered, and is shown to be a technically viable, economically attractive option. The accuracy transfer function of the observer estimate is used to evaluate its measurement performance. Comparative disturbance rejection is evaluated by overlaying the dynamic stiffness (inverse of output impedance) frequency response of each controller on a single plot. Experimental results for one controller are presented.

[1]  D. Divan,et al.  Discrete pulse modulation strategies for high-frequency inverter systems , 1989, 20th Annual IEEE Power Electronics Specialists Conference.

[2]  N. Abdel-Rahim,et al.  A single-phase voltage-source utility interface system for weak AC network applications , 1994, Proceedings of 1994 IEEE Applied Power Electronics Conference and Exposition - ASPEC'94.

[3]  Ying-Yu Tzou,et al.  Sliding mode control of a closed-loop regulated PWM inverter under large load variations , 1993, Proceedings of IEEE Power Electronics Specialist Conference - PESC '93.

[4]  G. Joos,et al.  A two switch high performance current regulated DC/AC converter module , 1990, Conference Record of the 1990 IEEE Industry Applications Society Annual Meeting.

[5]  E. Levi,et al.  Reduction of the output impedance of PWM inverters for uninterruptible power supply , 1990, 21st Annual IEEE Conference on Power Electronics Specialists.

[6]  D. Luenberger An introduction to observers , 1971 .

[7]  Thomas A. Lipo,et al.  Motion control with induction motors , 1994 .

[8]  A. Skjelines,et al.  Matching a UPS to the computer market , 1989, Conference Proceedings., Eleventh International Telecommunications Energy Conference.

[9]  S. D. Finn A high performance inverter technology, architecture and applications , 1993, Proceedings Eighth Annual Applied Power Electronics Conference and Exposition,.

[10]  Robert D. Lorenz,et al.  A high performance sine wave inverter controller with capacitor current feedback and "back-EMF" decoupling , 1995, Proceedings of PESC '95 - Power Electronics Specialist Conference.

[11]  Atsuo Kawamura,et al.  Waveform compensation of PWM inverter with cyclic fluctuating loads , 1988 .

[12]  Atsuo Kawamura,et al.  Instantaneous Feedback Controlled PWM Inverter with Adaptive Hysteresis , 1984, IEEE Transactions on Industry Applications.

[13]  G. Sciutto,et al.  A new PWM control sys­tem for UPS using hysteresis com­pa­rator , 1987 .